![background image](http://html.mh-extra.com/html/bosch/d9068/d9068_operation-and-installation-manual_38835004.webp)
D9068
|
Operation and Installation Guide | Contents
4
Bosch Security Systems, Inc. | 3/13 | F01U071094-0
7
Table 1: Programming Features
Program Feature or
Option
Permitted in
UL864? (Yes/No)
Possible Settings
Settings Permitted in
UL864
Auto Test
Frequency
Yes
1)
4 h
2)
12 h
3)
24 h
4)
7 days
5)
28 days
6)
Disabled
1)
4 h
2)
12 h
3)
24 h
Program Relay
Yes
1)
Release on Trouble
2)
Activate on Ground
Start
1)
Release on Trouble
AC Fail Delay
Yes
1)
Wait for DC
2)
Wait Delay Time
0-24 h
2)
Wait Delay Time 1-3 h
Phone Line Monitor
for Each Line
Yes
0)
No
1)
Yes
1)
Yes
Response Time
Yes
1) Fast (0.5 sec)
2) Programmed
1)
Fast (0.5 sec)
2)
1-9 sec