D9068
|
Operation and Installation Guide | 5.0 Programming
48
Bosch Security Systems, Inc. | 3/13 | F01U071094-0
7
4.
The current setting appears in
parentheses on the first line. Using
the keypad, enter a value from 1 to
9, or press [Test] for a list of
hexadecimal entries. Pressing [Test]
shows the window:
SELECT HEX CODE
1: HEX A
2: HEX B
3: HEX C
4: HEX D
5: HEX E
6: HEX F
Use the programming procedure
for 4/2 reporting codes in
Groups 2 to 5. Refer to
for definitions of each 4/2
reporting code.
3: SIA SILENC RPT
To access
SIA SILENC RPT
, select
[0]:
PROGRAM
[6]: PROG FORMATS
[3]: SIA
SILENC RPT
. When using SIA reporting,
all reporting codes except one are fixed
and do not require programming. The
Silence Report is not a standard SIA
code and can be programmed.
Use hexadecimal numbers to enter the
required ASCII value. Enter one number
for the left character or byte and
another number for the right character
or byte.
Use the factory default KB = 0B x 4B, 0B
x 42B.
Refer to a standard table of ASCII
values. All data that is entered
consists of hexadecimal values. The SIA
event codes use characters ranging from
A to Z.
To program SIA event codes for the
Silence Report:
1.
At the Prog Formats submenu, press
[3] to select
3: SIA SILENC RPT
. The
window shows:
SIA SILENC RPT
1: LEFT BYTE
2: RIGHT BYTE
2.
Press the number key that corresponds
with your selection. In this example,
1: LEFT BYTE
is selected. The window
shows:
LEFT BYTE (___)
0-9, <TEST>:
3.
The current setting appears in the
parentheses on the first line. Enter
a hexadecimal value and press
[# Command].
4.
To view the hexadecimal codes, press
[Test]. The window shows:
SELECT HEX CODE
1: HEX A
2: HEX B
3: HEX C
4: HEX D
5: HEX E
6: HEX F
Program 2: RIGHT BYTE using
the same procedure as
programming SIA event codes
for the Silence Report.
5.4.7 PROG DEFLTS
PROG DEFLTS
1: CLEAR HISTORY
2: DEFAULT ALL EE
3: DEFLT 4/2 CDES
The
PROG DEFLTS
feature clears the
history logger, resets the D9068 to its
default EEPROM settings, and applies
default reporting codes.
1: CLEAR HISTORY
To access
CLEAR HISTORY
, select
[0]: PROGRAM
[7]: PROG DEFLTS
[1]: CLEAR HISTORY
. You can clear some
or all of the history records in the
system using this option.
To clear the history logger, reset the
D9068 to default settings, and apply
default reporting codes:
1.
At the Prog Defaults submenu, press
[1] to select
1: CLEAR HISTORY
. The
window shows:
HIST ITEMS= _____
DEL OLDEST ###
2.
The number on the first line shows
the total number of records stored in
the history logger. Enter the number
of history records you want to delete
and press [# Command]. Those events
are erased and the D9068 returns to
the Prog Defaults Menu.
2: DEFAULT ALL EE
To access
DEFAULT ALL EE
, select
[0]: PROGRAM
[7]: PROG DEFLTS
[2]: DEFAULT ALL EE
.
This option allows you to set the D9068
to the original factory programming
configuration.