D9068
|
Operation and Installation Guide | Appendix F: D8024/D10024/D10024A Analog
FACP Operation
72
Bosch Security Systems, Inc. | 3/13 | F01U071094-0
7
F.4.7 Reported Event to FACP Cause Mapping
lists the events generated by a D8024 and D10024/D10024A Analog FACP and
the causes of the events.
Table 23: Analog Reports and Causes
Analog FACP
Event
Comments
Cause
Point Fire Alarm Control panel
generated.
There is a point zone alarm.
Point
Supervisory
Alarm
Control panel
generated.
There is sprinkler supervisory input.
Point Monitor
Alarm
Control panel
generated.
An alarm from the point is programmed as type =
monitor.
Point Fire
Trouble
Control panel
generated.
Any point trouble.
Point Fire Dirty
Report
Control panel
generated.
Any point is dirty.
Point Fire
Disable
Control panel
generated.
Any point disabled.
System Test
Control panel
generated.
The Walk Test or Output Test entered.
System Test
Restore
Control panel
generated.
The Walk Test or Output Test exited.
Silence
Control panel
generated.
Only Silence reported; resound not reported.
Fire Drill
Control panel
generated.
A fire drill initiated (local and remote).
Open Reset
Dialer generated.
The control panel reset.
Low Battery
Control panel
generated.
A low battery is detected.
AC Fail
Control panel
generated.
There is an AC Fail (after the control panel and
dialer time-outs).
Auto Test
Dialer generated.
An Auto Test is in progress.
Off Normal at
Test
Dialer generated.
Control panel trouble occurred when the Test
Report was sent.
Phone 1 Trouble
Dialer generated.
There is trouble on Phone Line 1.
Phone 1 Restore
Dialer generated.
The line is restored.
Phone 2 Trouble
Dialer generated.
There is trouble on Phone Line 2.
Phone 2 Restore
Dialer generated.
The line is restored.
Manual Comm Test Dialer generated.
The Communications Test is in progress.
Data Lost
Dialer generated.
There is a communication error.
EEPROM Failure
Dialer generated.
There is an EEPROM failure.
System Reboot
Reset
Control panel
generated.
All trouble and alarms are cleared. This message
is sent when the D9068 receives an all clear
message from the control panel after the control
panel resets.
Trouble Input
Trouble.
Trouble Input
Restore
Trouble is stored.
Equipment Fail
Control panel
generated.
This message occurs for several trouble type
events. To identify the specific type of trouble
that the condition parameter uses, refer to
on page 59. Look for the Equipment Fail
(Restore) Reports. Not all events have an
equivalent Equipment Restore message.
Equipment
Restore
Control panel
generated.