D9068
|
Operation and Installation Guide | Appendix C: Fire Communicator Report
Summary
58
Bosch Security Systems, Inc. | 3/13 | F01U071094-0
7
Table 14: Reporting Summaries (Continued)
Point-Related Events
Report
Description
SIA
Code
SIA
Description
Contact
ID Code
Contact ID
Description
4/2
Code
Default
Values
Modem IIIa
2
Description
AC Fail
AT
AC Trouble
1 301 aa
000
AC Loss
F8
AC Fail
AC Fail
Restore
AR
AC Restoral
3 301 aa
000
AC Loss
E8
AC Restoral
Auto Test
RP
Automatic
Test
1 602 aa
000
Periodic
Test Report
EE
Test Report Non
Expanded
Off Normal at
Test
YX
Service
Required
6 300 aa
000
System
Trouble
FD
Test-Off Normal Non
Expanded
Phone 1
Trouble
LT 1
Phone Line
Trouble
1 351 aa
000
Telco 1
Fault
FB
Phone Line
Fail Phone Line = 1
Phone 1
Restore
LR 1
Phone Line
Restoral
3 351 aa
000
Telco 1
Fault
EB
Phone Line Restoral
Phone Line = 1
Phone 2
Trouble
LT 2
Phone Line
Trouble
1 352 aa
000
Telco 2
Fault
FC
Phone Line
Fail Phone Line = 2
Phone 2
Restore
LR 2
Phone Line
Restoral
3 352 aa
000
Telco 2
Fault
EC
Phone Line
Restoral Phone Line
= 2
System
Trouble
IA
Equipment
Failure
Condition
1 300 aa
000
System
Trouble
FD
Equipment Fail
System
Trouble
Restore
IR
Equipment
Fail
Restoral
3 300 aa
000
System
Trouble
ED
Equipment Restoral
Fire Drill
Start
FI
Fire Test
Begin
1 607 00
000
Walk Test
Mode
F2
Fire Walk Start ID:
0000
Fire Drill
End
FK
Fire Test
End
3 607 00
000
Walk Test
Mode
Restore
E2
Fire Walk End ID:
0000
System Test
TS
Test Start
1 607 aa
000
Walk Test
Mode
26
Walk Test Start
System Test
Restore
TE
Test End
3 607 aa
000
Walk Test
Mode
Restore
27
Walk Test End
Silence
KB
Heat/Bypass
1 607 aa
000
Open/Close
1F
Alarm Silence
Manual Test
RX
Manual Test
1 601 aa
000
Manual
Trigger
Test
FE
Test Report Non
Expanded
Data Lost
RT
Data Lost
1 354 aa
000
Fail to
Communicate
FF
Communications
Fail *
EEPROM
Failure
IA 4
Equipment
Failure
Condition
1 307 aa
000
Self Test
Failure
FD
Parameter Checksum
Fail
Trouble Input
IA 2
Equipment
Failure
Condition
1 300 aa
002
System
Trouble
FD
Equipment Fail COND
= 002
Trouble Input
Restore
IR 2
Equipment
Fail
Restoral
3 300 aa
002
System
Trouble
ED
Equipment
Restoral COND = 002
System
Trouble
Keypad
IA 5
Equipment
Failure
Condition
1 300 aa
005
System
Trouble
FD
Equipment Fail Cond
= 005
System
Restore
Keypad
IR 5
Equipment
Fail –
Restoral
3 300 aa
005
System
Trouble
ED
Equipment
Restoral Cond = 005
System
Trouble Comm
Fault
IA 6
Equipment
Failure
Condition
1 300 aa
006
System
Trouble
FD
Equipment Fail Cond
= 006
System
Restore Comm
IR 6
Equipment
Fail
3 300 aa
006
System
Trouble
ED
Equipment
Restoral Cond = 006