D7024
| Operation and Installation Guide | 7.0 Control Panel Programming
Bosch | 7/05 | 31499J
45
7.4.3
Point Copy
Shortcut:
0
-PROG >
4
-PROG INPUTS >
3
-POINT COPY
This feature copies the settings you entered for one
point to one or more other points.
The following window appears:
1.
Enter the point you want to copy from and press
[#].
2.
Enter the first point you want to copy to and press
[#].
3.
Enter the last point you want to copy to and press
[#].
The PROG INPUTS Menu appears.
This feature does not copy the description. Point copy is
only intended for use on input points. Do not copy from
an output point (future use) or copy over a programmed
output point. The copy operation automatically stops,
with an error message, if outputs are encountered.
While copying to a large number of points, the remote
keypads might briefly display
SYSTEM FAULT
because
they are not updated during the copy operation.
7.5
PROG Outputs
7.5.1
Programming NACs
Shortcut:
0
-PROG >
5
-PROG OUTPUTS >
1
-NACs
The main panel includes two local NACs, NAC 1 and
NAC 2. The D7024 can also support up to two D7038
Remote NAC Power Supplies offering a total of eight
remote NACs, for NACs for each RNAC.
The following window appears:
Press the number key corresponding to your selection.
Local NACs
Shortcut:
0
-PROG >
5
-PROG OUTPUTS >
1
-NACs
The display scrolls through the NAC options.
1.
Press [1] for LOCAL to access:
Onboard NAC 3, NAC 4 are not currently supported.
2.
Press the number key corresponding to your
selection.
The display scrolls through the following:
3.
Press the number key corresponding to your
selection.
When [2] is selected from the PROG NACs Menu,
the following selections scroll:
COPY FROM
POINT:_ _ _
COPY TO FIRST
POINT:_ _ _
COPY TO LAST
POINT:_ _ _
1- NACs
2- RELAYS
PROG OUTPUTS
NAC OUTPUTS
1- LOCAL
2- REMOTE 1
3- REMOTE 2
ONBOARD NAC
1- NAC #1
2- NAC #2
3- NAC #3
4- NAC #4
PROG NAC
4- (reserved)
5- CONFIGURATION
6- ZONE ASSIGNS
NAC CONFIG ()
1- STEADY
2- PULSING
3- TEMPORAL
4- WHEELOCK
5- GENTEX