D7024
| Operation and Installation Guide | 13.0 Appendix D: Programming Defaults List
Bosch | 7/05 | 31499J
75
13.0 Appendix D: Programming
Defaults List
PROG TIME
SYSTEM: Last date in EE 0000
AUTO TEST
TEST TIME: 0200
TEST FREQ: 24 hours
DAYLIGHT SAV: 2- enable
SECURITY
PINS
PROGRAMMER: 9876
USERS: User 1 = 1234, User 2 = 0000
AUTHORITY
USER 1: 2
OTHERS: 0
PROG SYSTEM
TIMERS
SMOKE RESET: 6 sec
AC FAIL DELAY: 6 h
AUTO SILENCE: 0 min
DISPLAY RATE: 4 x 0.25 = 1 sec
AC LINE SYNCH2 (60- Hz)
OPTION BUS
UPDATE BUS: Queries both option buses and
updates list of connected devices.
SETUP KEYPAD: 0
PIN REQUIRED:
LOCAL: No
REMOTE: Yes
REMOTE PGM: 0- DISABLE
PROG INPUTS
POINT NUMBER (1 to 4, 5 to 8, 9 to 255)
FUNCTION
Point Function 1 = 1
Point Function 2 = 2
Point Function 3 = 3
Point Function 4 = 4
Point Function 5 = 5
Point Function 6 = 6
Point Function 7 = 7
Point Function 8 = 8
Point Function 9 - 255 = 10
ALARM/TROUBLE: Trouble On Open
OUTPUT ZONE
Point Zone 1 = 1
Point Zone 2 = 2
Point Zone 3 = 3
Point Zone 4 = 4
Point Zone 5 = 5
Point Zone 6 = 6
Point Zone 7 = 7
Point Zone 8 = 8
Point Zone 9 - 19 = 9
Point Zone 20 - 39 = 10
Point Zone 40 - 59 = 11 etc.
VERIFICATION: No
LATCHING: Yes (Point 4 = No)
POINT FUNCTION (1 to 16)
PROG OUTPUTS
NACs
NAC #1:
CONFIGURATION: Temporal
ZONE ASSIGNS:
Zone A: 53
Zone B: 0
Zone C: 0
Zone D: 0
NAC #2:
CONFIGURATION: Steady
ZONE ASSIGNS:
Zone A: 53
Zone B: 0
Zone C: 0
Zone D: 0
RNAC 1
Outputs 1, 2, 3, 4
Configuration: Steady
Zone Assignment:
Zone A: 53
Zone B: 0
Zone C: 0
Zone D: 0
1 to 3,
5 to 10,
3 to 16
4
11
12
CONFIGURE
fire
water
supv
monitor
LOCAL ONLY
no
no
no
no
SILENCE-
ABLE
no
no
no
no
LOOP
REPSONSE
fast
16s
fast
fast