D7024
| Operation and Installation Guide | 7.0 Control Panel Programming
Bosch | 7/05 | 31499J
51
Dialing Type
Shortcut:
0
-PROG,
6
-PROG ACC'NTS,
2
-PHONE CONTROL
This feature determines the format the control panel
uses for dialing on each telephone line. First, the tone
and pulse setting attempt tone dialing, and if that fails,
switches to pulse dialing.
1.
Select Line 1 or Line 2.
The display scrolls through the Phone Control
options.
2.
Press [2] for DIALING TYPE and to access:
3.
Press the number key corresponding to your
selection.
The preceding window appears.
7.6.3
Report Steering
Shortcut:
0
-PROG >
6
-PROG ACC'NTS >
3
-RPT STEERING
You can direct the classes of reports to different
telephone numbers. Non-supervisory alarms include fire
alarms, waterflow alarms, and monitor alarms.
Supervisory alarms come from points configured as a
supervisory type. Non-supervisory restorals include fire,
waterflow, and monitor restorals. Supervisory restorals
only come from points configured as a supervisory type.
Trouble reports include all point and system troubles
and restorals. Tests include the Auto Test, Manual Test,
and Off-Normal at Test reports. The control panel
allows the Silence Report, Reset Report, and Drill
Report to be individually directed.
The display scrolls through the following items:
1.
Press the number key corresponding to your
selection.
The following window appears with the headings
depending on your choice. In the example, the
non-supervisory alarm is selected:
•
PHONE 1 ONLY: Report sent to Phone #1
only.
•
PHONE 2 ONLY: Report sent to Phone #2
only.
•
PHONE 1 AND 2: Report sent to Phone
Numbers 1 and 2.
•
PHONE 2 BACKUP: Report sent to Phone #1,
then to Phone #2 if #1 fails.
•
NO REPORT: No report sent.
2.
Press the number key corresponding to your
selection.
The preceding window appears.
7.6.4
Ring Count
Shortcut:
0
-PROG >
6
-PROG ACC'NTS >
4
-RING COUNT
The following window appears:
Enter the information and press [#/CMND] to access
the preceding window. Press [0] [0] to disable ring
detection.
If any reports are directed to Phone Number 2
(including the default, Phone 2 backup), a
telephone number and account number must
be programmed for Phone Number 2. The
control panel indicates a Comm Fault if it
sends a report (using Phone Number 1
parameters) that references unprogrammed
Phone Number 2 parameters.
PHONE CONTRO (_ _)
1- PULSE ONLY
2- TONE/PULSE
3- TONE ONLY
The number of rings before the control panel
seizes the line to attempt remote program-
ming must remain set to “0” for UL 864 local,
auxiliary, or remote station installations.
REPORT STEERING
1- NONSUP ALRM
2- SUPVSRY ALRM
3- NONSUP RSTR
4- SUPVSRY RSTR
5- TROUBLE
6- TESTS
7- SILENCE
8- RESET
9- FIRE DRILLS
NONSUP ALRM(_ _)
1- PHONE 1 ONLY
2- PHONE 2 ONLY
3- PHON 1 AND 2
4- PNN 2 BACKUP
5- NO REPORT
RING COUNT
(01-15,00=DIS)_ _ _