D7024
| Operation and Installation Guide | 8.0 Installation Guide for UL Listed Systems
62
Bosch | 7/05 | 31499J
D184A Local Energy Kit
The D184A is a UL Listed module that connects local
energy signaling devices to the D7024 for auxiliary
service operation. Refer to the
D184A Installation Guide
(P/N: 41175) for more information.
D185 Reverse Polarity Module
The D185 Reverse Polarity Module is a UL Listed
module connecting the control panel with either a single
set or a pair of leased telephone company (Telco) lines
in NFPA 72 remote station applications. It relays system
alarm status information from the control panel to a
monitoring station. The D185 operates with either 12 or
24 VDC supply.
The D185 can signal alarm, trouble, and supervisory
conditions (refer to the
D185 Installation Manual
(P/N:
32906) for details).
Figure 22
shows the module being used to signal alarm
and trouble conditions only. With a third relay, available
from the eight-relay expansion module and an
additional leased line, supervisory conditions can also
be signaled.
In this example, Relay 1 must be programmed to
operate on Alarm (Zone 63) and Relay 2 must be
programmed to operate on Trouble (Zone 62). Input 4 is
programmed as a monitor point. Any alarm interrupts
the voltage to the monitoring station. Placing the D185
in Test Mode causes a MONITOR TROUBLE 4.
Figure 22: Wiring the D185
1 – D185 Module
2 – To monitoring station
3 – Black wire
4 – Yellow wire
5 – Blue wire
6 – D275 EOL
7 – 2.21 k
Ω
EOL (P/N: 25899)
8 – Fire panel
GND PWR
-
PWR
+
TRBL
TRIG
SUPV
TRIG
ALRM
TRIG
SUPV
+
SUPV
-
ALRM
-
ALRM
+
GND SUPV
ZONE
1
2
3
4
5
6
7
8
9
10
11
12
31
NC 2
30
RELAY 2
COM 2
27
26
RELAY 1
COM 1
NO 1
25
24
SMOKE
POWER
21
EARTH
GROUND
SMK+
SMK-
20
19
4-
L+
18
3-
INPUT
POINTS
1
2
3
4
5
5
6
7
8