| Operation and Installation Guide | 7.0 Control Panel Programming
58
Bosch | 7/05 | 31499J
Verify that only the expected number of points was
removed from the system. Points removed from the
control panel's site-specific configuration do not operate
and cannot be supervised even if they are returned to
the bus.
When Point Delete is complete, auto programming
automatically checks for new devices on the buses. A
new device is found when it is present on one of the
multiplex buses, but its address is not programmed into
the control panel's site-specific memory. If a new device
is detected, the D7024 shows the following menu (where
“xxx” is the address of the first new device found):
This menu allows the device type to be defined. Press
the number key corresponding to the device type
installed at the address. If a detected device should not
be installed and left inactive, press [0] to bypass the new
device.
All inputs are configured to use Point Function 10 as
they are added. Points added during Auto Programming
are not configured for the following operation:
•
Point Function 10 (Fire Alarm, Fast Response, Non-
silenceable, Not Local-only)
•
Open Status = Trouble
•
Output Zone 9
•
Alarm Verify = NO
•
Latching = YES
You can change input point programming when Auto
Programming completes using the Input-Programming
Menu.
When I/O modules are added during Auto
Programming, the relay (second point) is configured to
activate on any alarm, non-silenceable (Zone 63). You
can change this when Auto Programming completes
using the Output-Programming Menu.
As new devices are added, the D7024 performs some
basic error checks. The following errors can appear
when adding a device:
In the preceding message, “xxx” is replaced by the
affected address, and “#” is replaced by a code number
that indicates the type of error.
Table 31
identifies the
auto programming error messages.
When the point-add operation is complete, the D7024
shows the total number of points added to the control
panel for a period of 5 sec. Verify the number of devices
added matches the expected number.
Ensure the correct device type is selected for
each point. Incorrectly specified device types
can cause multiplex devices to malfunction or
fail to operate.
NEW DEVICE @ xxx
2 SINGLE INPUT
3 I/O MODULE
4 MUX SMOKE
5 SMOKE W/FRZ
6 - DUAL INPUT
7 - OCTAL INPUT
0 NO DEVICE
Table 31:
Auto Programming Error Messages
Code
Error
Description
1
New point is
under an exist-
ing point.
The new point is in the space
required for an existing multi-
address device. This is checked
when auto programming first
starts.
2
Point overlaps
existing point.
There are already devices con-
figured at one of the addresses
required for the new multi-point
device.
3
Point is at an
illegal address.
The addresses at which multi-
address devices can be installed
are restricted. Refer to Refer to
Table 7
on page 13 or the spe-
cific device's installation instruc-
tions for details.
4
Too many mul-
tiplex relays.
Only 20 I/O devices can be sup-
ported on a given bus.
If a new device is not detected on the bus
during the point-add operation, the device
does not operate and does not generate trou-
ble conditions even if it remains connected to
the bus.
ADDRESS ERROR #
AT ADDRESS xxx
AUTO PROGRAM
xxx POINTS ADDED