| Operation and Installation Guide | 2.0 Overview
Bosch | 7/05 | 31499J
9
2.8
Users
The system allows up to 16 users, or up to 100 users with the D7039 installed. A personal identification number
(PIN), the four-digit code entered at the keypads, and an authority level determine which functions are performed
can be assigned to each user. Refer to
Section 5.6 Personal Identification Numbers
on page 28.
2.9
Lightning Protection
Metal oxide varistors (MOVs) and spark gaps provide protection from lightning surges and static discharges.
2.10
Backup Battery Calculation
Table 3
is used to calculate the standby battery capacity required by NFPA when using the D7024.
Figure 2:
Supplemental Reporting
1 – Jumper from R1 to R2
2 – Jumper from T1 to T2
3 – House telephone
4 – Telco line
R2
HR2
HT2
T2
R1
RH1
TH1
T1
1
2
4
3
This system is intended for installation entirely within one building.
Table 3:
Standby Battery Capacity Calculations
Device
Quantity
Standby
Current/ Device
Total
Standby
Alarm
Current/Device
Total
Alarm
D7024 Control Panel
1
200 mA
200 mA
380 mA
380 mA
D184 Local Energy Kit
10 mA
0.45 mA
D7014 B to A Initiating Circuit Converter
11 mA
11 mA
D7015 B to A NAC Converter
1 mA
46 mA
D7034 4-Point Expander
44 mA
160 mA
D7035/B Octal Relay
8 Ma + 30 mA*
8 Ma + 30 mA*
D7048/B Octal Driver Module
10 mA
10 mA
D7036 Annunciator Keypad
80 mA
100 mA
D7031 Remote Keyswitch
0 mA
0 mA
D7030X 8-Point LED Annunciator
27 mA
132 mA
D7030X-S2 8-Point LED Annunciator
35 mA
175 mA
D7030X-S8 8-Point LED Annunciator
35 mA
175 mA