D7024
| Operation and Installation Guide | 12.0 Appendix C: Fire Communicator Reporting Summary
Bosch | 7/05 | 31499J
73
When the Modem IIIa
2
, SIA, or Contact ID reporting formats are used, an additional numeric identifier is
transmitted with system trouble messages to provide a specific indication of the particular fault. This identifier is also
recorded in the History Log.
Table 36
lists the numeric identifiers.
PHONE 1 TROUBLE
52
dd/dd tt:tt ql ACCT aaaa PHONE LINE FAIL
+++ ACCT aaaa PHONE LINE=1
PHONE 1 RESTORE
53
dd/dd tt:tt ql ACCT aaaa PHONE RESTORAL
+++ ACCT aaaa PHONE LINE=1
PHONE 2 TROUBLE
54
dd/dd tt:tt ql ACCT aaaa PHONE LINE FAIL
+++ ACCT aaaa PHONE LINE=2
PHONE 2 RESTORE
55
dd/dd tt:tt ql ACCT aaaa PHONE RESTORAL
+++ ACCT aaaa PHONE LINE=2
SYSTEM TROUBLE
56
dd/dd tt:tt ql ACCT aaaa EQUIPMENT FAIL
+++ ACCT aaaa SDI=001 COND=ccc
SYSTEM TROUBLE RESTORE
57
dd/dd tt:tt ql ACCT aaaa EQUIP RESTORAL
+++ ACCT aaaa SDI=001 COND=ccc
MANUAL TEST
58
dd/dd tt:tt ql ACCT aaaa TEST REPORT
DATA LOST
59
dd/dd tt:tt ql ACCT aaaa COMM FAIL
+++ ACCT aaaa PHONE#=1
EEPROM FAILURE
60
dd/dd tt:tt ql ACCT aaaa EQUIPMENT FAIL
+++ ACCT aaaa SDI=001 COND=18
EEPROM RESTORAL
61
dd/dd tt:tt ql ACCT aaaa EQUIP RESTORAL
+++ ACCT aaaa SDI=001 COND=18
SMOKE POWER FAULT
62
dd/dd tt:tt ql ACCT aaaa EQUIPMENT FAIL
+++ ACCT aaaa SDI=001 COND=3
SMOKE POWER RESTORE
63
dd/dd tt:tt ql ACCT aaaa EQUIP RE++ ACCT aaaa
SDI=001 COND=3
REMOTE PROGRAMMING FAIL
66
dd/dd tt:tt ql ACCT aaaa RAM ACCESS FAIL
REMOTE PROGRAMMING SUC-
CESS
67
dd/dd tt:tt ql ACCT aaaa RAM ACCESS OK
Note:
dd/dd tt:tt - Date and time; aaaa = Account number; uuu = User ID; zzz = Point; ccc = Numeric identifier
Table 35:
Receiver Output
Table 36:
Numeric Identifiers
Condition
Identifier in
History Log
(reported with
System
Trouble Report)
Condition
Identifier in
History Log
(reported with
System
Trouble Report)
Option bus device at address 1 failed.
2
User disabled multiplex bus outputs.
45
Option bus device at Address 2 failed.
3
User disabled dialer.
46
Option bus device at Address 3 failed.
4
User disabled Relay 1.
47
Option bus device at Address 4 failed.
5
User disabled Relay 2.
48
Option bus device at Address 5 failed.
6
User disabled remote relay module 1.
49
Option bus device at Address 6 failed.
7
User disabled remote relay module 2.
50
Option bus device at Address 7 failed.
8
Class “A”, Style 6 wiring failure on MUX
bus.
51
Option bus device at Address 8 failed.
9
MUX bus A (9 to 128) failed.
52
Option bus device at Address 9 failed.
10
MUX bus B (129 to 255) failed
53
Option bus device at Address 10 failed.
11
MUX module processor failure.
54
Option bus device at Address 11 failed.
12
Rremote NAC module 1, output 1 wiring
fault.
55