D7030X-S8 Eight Point
LED Annunciator
An eight-zone LED annunciator with all eight zones reserved for supervisory functions. It has Power
and Trouble LEDs plus eight zone LEDs that can be individually labeled.
D7031 Remote Key-
switch
Allow you to silence notification appliances and reset the control panel from a remote location.
D7032 Eight Point LED
Annunciator Expander
(future release)
Attaches to a D7030X and identifies the location of a fire alarm for eight additional zones. Up to
eight are allowed for each system.
D7033 Four-Wire Alpha-
numeric LCD Keypad
Connects to either four-wire option bus, up to four allowed for each system.
D7034 Four Point
Expander
Allows the D7024 FACP to support four additional points. The D7034 plugs into the control panel
and provides four Class “B”, Style B loops identical in characteristics to the loops on the control
panel. One D7034 is allowed for each system.
D7035/B Octal Relay
Module
Allows eight Form “C” Relay outputs to be added to the system. The outputs are fully programmable
and can be activated by system events.For complete flexibility, each output operates independently
of the other seven. The D7035 connects to the option bus, up to two allowed for each system.
Refer to the
D7035 Installation Guide
(P/N: 37280) for the required enclosure modification. The
D7035B is pre-installed on a mounting skirt.
D7036 Fire Annunciator
Keypad
A four-wire LCD annunciator keypad used with the D7024 to establish the location of a fire alarm.
D7038 Remote NAC
Power Supply
Adds four NFPA 72 Class “B”, Style Y NACs through the option bus, and is supervised by the con-
trol panel. Connects to either four-wire option bus of the D7024 Control Panel, up to two allowed
for each system.
D7039 Multiplex Expan-
sion Module
Provides either two, two-wire (Class “B”, Style 4) multiplex buses or one, four-wire (Class “A”, Style
6) multiplex bus. In Class”A” Mode, up to 120 additional addressable points can be added. In Class
“B” Mode, up to 240 additional addressable points can be added. Connects directly to the control
panel, allowing one for each system.
D7042B Eight-Input
Remote Module
Provides eight Class “B”, Style B input points. Up to 15 modules can be connected to MUX Bus A,
and 15 on MUX Bus B. The D7042 is powered by 12 VDC supplied by the option bus power termi-
nals, in addition to the two-wire data connection. Do not use the D7042 on an SLC configured for
Class “A”, Style 6 operation.
D7048B Octal Driver
Module
Provides eight open collector transistor outputs for addition to the D7024 FACPs. It connects to
the control panels through the option bus.
D7045 Mux Pull Station
UL Listed fire alarm initiating device.
D7044 Mux Single Input
Fire
General purpose device connecting a contact device to the control panel’s multiplex bus with a
supervised local loop. All operating power for the D7044 is drawn from the control panel.
D7044M Mux Mini
Contact Module
A general purpose device connects a contact device to the control panel’s multiplex bus with a
supervised input loop. All operating power for the D7044M is from the control panel.
D7052 Mux Dual Input
Fire
A general purpose device connecting to the control panel’s multiplex bus. It provides two super-
vised input zones for connecting conventional normally-open (NO) inputs. All operating power for
the D7052 is from the control panel.
D7053 Mux I&O Module
Fire
A general purpose device connecting the control panel’s multiplex bus. It implements a supervised
local loop, and a Form “C” Relay output. Up to 20 modules can be connected to each MUX bus. All
operating power for the D7053 is from the control panel.
Table 6: