D7024
| Operation and Installation Guide | 7.0 Control Panel Programming
Bosch | 7/05 | 31499J
47
3.
Press the number key corresponding to your
selection.
4.
After programming the local NACs, the preceding
window appears.
7.5.2
Programming Relays
Shortcut:
0
-PROG >
5
-PROG OUTPUTS >
2
-RELAYS
The main panel includes two onboard relays, Relay 1
and Relay 2. The D7024 can also support up to two
D7035 Octal Relay Modules (Remote Relay 1 and
Remote Relay 2), offering a total of 16 remote relays
(eight relays for each module).
The following window appears:
Press the number key corresponding to your selection.
Local Relays
Shortcut:
0
-PROG >
5
-PROG OUTPUTS >
2
-RELAYS
The display scrolls through the Relay options.
1.
Press [1] for LOCAL to access:
2.
Enter the number corresponding with the relay you
want programmed and press [#].
The display prompts you to enter four zones to
activate this output:
3.
Enter the first zone (00 to 63) you want to map to
drive this output and press [#].
A similar display for Zone B, C, and D appears,
allowing up to four zones to drive this output.
4.
When all four zones are assigned, the preceding
window appears.
Remote Relays
Shortcut:
0
-PROG >
5
-PROG OUTPUTS >
2
-RELAYS
The display scrolls through the relay options.
1.
Press [2] for REMOTE 1 or [3] for REMOTE 2 to
access:
Table 23:
Remote NAC Configuration
Configuration Description
Steady
Output is programmed to turn on steady
for a fire alarm.
Pulsing
Output is programmed to pulse for a fire
alarm in the normal manner.
Temporal
Output is programmed to pulse for a fire
alarm in Temporal 3.
Zone
Assignment
Each output can be assigned up to four
zones; Zone A, B, C, or D.
00 = disabled, 1 to 63.
The Multiplex Relay Programming option is
only visible if the D7039 Multiplex Expander is
installed, and is reserved for future use.
1- LOCAL
2- REMOTE 1
3- REMOTE 2
4- MULTIPLEX
RELAY OUTPUTS
ONBOARD RELAY
(1-2):
Table 24:
Pre-Assigned Zone Quick Reference
Zone
Pre-Assigned Condition
52
General Fire Alarm (non-silencing)
53
General Fire Alarm (silencing)
54
Ground Start
57
Communication Trouble
58
General Supervisory Alarm (non-silencing)
59
Alarm Verification
60
AC Failed
61
General Waterflow Alarm (non-silencing)
62
General Trouble
63
General Fire Alarm, Monitor, Waterflow supervisory
(non-silencing)
An output point cannot be assigned to more
than four zones. It is not necessary to map
each output to four zones. Each zone can
have several outputs mapped to it.
The @_ shows the relay module address in
the system. The lower number address is
Relay 1, the higher address is Relay 2.
OUTPUT ZONE A (XX)
(00-63):
REMOTE RELAY @ X
(1-8):