# config -‐s config.alerts.alert2.sensor=temp
# config -‐s config.alerts.alert2.signal=DSR
# config -‐s config.alerts.alert2.type=pattern
UPS Power Status Alert
To trigger an alert when
myUPS
(on localhost) or
thatUPS
(on remote host
192.168.0.50
) power status changes between
on line, on battery and low battery.
# config -‐s config.alerts.alert2.sensor=temp
# config -‐s config.alerts.alert2.signal=DSR
# config -‐s config.alerts.alert2.type=ups
# config -‐s config.alerts.alert2.ups1=myUPS@localhost
# config -‐s [email protected]
Environmental and Power Sensor Alert
# config -‐s config.alerts.alert2.enviro.high.critical='critical value'
# config -‐s config.alerts.alert2.enviro.high.warning='warning value'
# config -‐s config.alerts.alert2.enviro.hysteresis='value'
# config -‐s config.alerts.alert2.enviro.low.critical='critical value'
# config -‐s config.alerts.alert2.enviro.low.warning='warning value'
# config -‐s config.alerts.alert2.enviro1='Enviro sensor name'
# config -‐s config.alerts.alert2.outlet#='RPCname'.outlet#
'alert2.outlet#' increments sequentially with each added outlet. The second 'outlet#' refers to the specific RPC
power outlets.
# config -‐s config.alerts.alert2.rpc#='RPC name'
# config -‐s config.alerts.alert2.sensor=[ temp | humid | load | charge]
# config -‐s config.alerts.alert2.signal=DSR
# config -‐s config.alerts.alert2.type=enviro
# config -‐s config.alerts.alert2.ups1='UPSname@hostname'
Example1: To configure a temperature sensor alert for a sensor called 'SensorInRoom42':
# config -‐s config.alerts.alert2.sensor=temp
# config -‐s config.alerts.alert2.enviro.high.critical=60
# config -‐s config.alerts.alert2.enviro.high.warning=50
# config -‐s config.alerts.alert2.enviro.hysteresis=2
# config -‐s config.alerts.alert2.enviro.low.critical=5
# config -‐s config.alerts.alert2.enviro.low.warning=10
# config -‐s config.alerts.alert2.enviro1=SensorInRoom42
# config -‐s config.alerts.alert2.signal=DSR
# config -‐s config.alerts.alert2.type=enviro
Example2: To configure a load sensor alert for outlets 2 and 4 for an RPC called 'RPCInRoom20':
# config -‐s config.alerts.alert2.outlet1='RPCname'.outlet2
# config -‐s config.alerts.alert2.outlet2='RPCname'.outlet4
# config -‐s config.alerts.alert2.enviro.high.critical=300
# config -‐s config.alerts.alert2.enviro.high.warning=280
# config -‐s config.alerts.alert2.enviro.hysteresis=20
# config -‐s config.alerts.alert2.enviro.low.critical=50
# config -‐s config.alerts.alert2.enviro.low.warning=70
# config -‐s config.alerts.alert2.rpc1=RPCInRoom20
# config -‐s config.alerts.alert2.sensor=load
# config -‐s config.alerts.alert2.signal=DSR