KB-206-1
28
Menu item
Function
Setting ex factory: 2.0 K
F2+F4⇒PAR⇒EMO⇒OHt
Modbus: 16435
Limit for maximum overheating on suction side
0.0 – 50.0 K
Setting ex factory: 25.0 K
F2+F4⇒PAR⇒EMO⇒Odt
Modbus: 164356
Limit for minimum/maximum overheating on suction side
0.0 – 50.0 K
Setting ex factory: 2.0 K
F2+F4⇒PAR⇒EMO⇒OAd
Modbus: 164437
Time delay for min. / max. overheating on suction side
0 – 60 min
Setting ex factory: 5 min
The ECOLITE controller monitors certain application
limits of the compressor or switches the compressor off
to protect it as soon as the application limits are ex-
ceeded.
When changing the refrigerant type (parameter Ert), the
ECOLITE controller sets the parameter dHA to the fol-
lowing presetting for the different refrigerants:
REF
R404A
R22
R134a
R507A
R407A
R407F
R450A
R448A
R513A
R449A
dHA
62°C
60°C
70°C
62°C
60°C
60°C
70°C
60°C
70°C
60°C
When changing the refrigerant type (parameter Ert), the
ECOLITE controller sets the parameter SLA to the fol-
lowing presetting for the different refrigerants:
REF
R404A
R22
R134a
R507A
R407A
R407F
R450A
R448A
R513A
R449A
SLA
-45°C
-45°C
-25°C
-45°C
-40°C
-40°C
-25°C
-40°C
-25°C
-40°C
If the cold store control is active, the monitoring of the
minimum and maximum overheating of the suction gas
is not possible and therefore deactivated.
Function of the digital inputs for external signals –
menu di:
Menu item
Function
F2+F4⇒PAR⇒di⇒i05
Modbus: 16448
Function of the first controller input for external signals
0 = no function (factory setting)
1 = reserved (do not use)
2 = enable condensing unit
3 = enable compressor
4 = enable condenser fan(s)
5 = set point adjustment active
6 = LowSound mode active
-1 = reserved (do not use)
-2 = enable condensing unit (inverted)
-3 = enable compressor (inverted)
-4 = enable condenser fan(s) (inverted)
-5 = set point adjustment active (inverted)