KB-206-1
26
Cold store control - menu COr:
Menu item
Function
F2+F4⇒PAR⇒COr⇒SP4
Modbus: 16424
Set point cold store temperature controller
-40.0 – 22.5°C
Setting ex factory: 2.0°C
F2+F4⇒PAR⇒COr⇒Crd
Modbus: 16425
Neutral band of cold store temperature controller
0.0 – 10.0 K
Setting ex factory: 1.0 K
The ECOLITE controller is equipped with a temperature
control, e.g. for a cold store. To measure the temperat-
ure, a BITZER NTC temperature sensor (10kΩ@25°C)
must be installed in the cold store and connected to the
electrical box of the condensing unit instead of the suc-
tion gas temperature sensor. During the cold store tem-
perature control, the suction pressure control is active
too. The suction pressure must be set to a sufficiently
low level.
Emergency service – menu EMO:
Menu item
Function
F2+F4⇒PAR⇒EMO⇒SME
Modbus: 16502
Enable operation without suction pressure transmitter
0 = operation mode deactivated
1 = operation mode activated
Setting ex factory: 0 = manual operation deactivated
F2+F4⇒PAR⇒EMO⇒dME
Modbus: 16503
Enable manual operation without high pressure transmitter
0 = operation mode deactivated
1 = operation mode activated
Setting ex factory: 0 = operation deactivated
F2+F4⇒PAR⇒EMO⇒AOE
Modbus: 16504
Enable substitute value for ambient temperature
0 = substitute value deactivated
1 = substitute value activated
Setting ex factory: 0 = substitute value deactivated
F2+F4⇒PAR⇒EMO⇒AO
Modbus: 16505
Substitute value for ambient temperature
-200.0 – 200.0°C
Setting ex factory: 25.0°C
F2+F4⇒PAR⇒EMO⇒COE
Modbus: 16506
Enable substitute value for cold store temperature
0 = substitute value deactivated
1 = substitute value activated
Setting ex factory: 0 = substitute value deactivated
F2+F4⇒PAR⇒EMO⇒CO
Modbus: 16507
Substitute value for cold store temperature
-200.0 – 200.0°C
Setting ex factory: 25.0°C
F2+F4⇒PAR⇒EMO⇒dOE
Modbus: 16508
Enable substitute value for discharge gas temperature
0 = substitute value deactivated
1 = substitute value activated