Electrical connection
Semi-hermetic compressor, condenser fan and elec-
trical accessories correspond to the EU Low Voltage
Directive 2014/35/EU.
The ECOLITE condensing unit is provided exclusively
for the connection to TN-C-S or TN-S three-phase
power supply systems with a nominal voltage 230/400
V Δ/Y at a nominal frequency of 50 Hz. The connection
of a neutral conductor is mandatory. A nominal supply
voltage with qualitative characteristics according to DIN
EN 50160 is required. The ECOLITE condensing unit is
provided for a stationary installation.
Type
Recommen-
ded fuse
Setting mo-
tor protec-
tion switch
LHL3E/2EES-2(Y)
18 A
8.0 A
LHL3E/2DES-2(Y)
10 A
9.5 A
LHL3E/2CES-3(Y)
13 A
11.0 A
LHL5E/4FES-3(Y)
13 A
11.5 A
LHL5E/4EES-4(Y)
16 A
14.5 A
LHL5E/4DES-5(Y)
16 A
16.0 A
LHL5E/4CES-6(Y)
20 A
20.0 A
Depending on the local conditions and applicable regu-
lations, the installation of a supply circuit disconnecting
device must be provided on site. The service switch
provided in the ECOLITE condensing unit does nor-
mally not fulfil the requirements regarding an electrical
disconnection of the device.
7.1
Schematic wiring diagram for ECOLITE
condensing units
Abbr.
Component
B1
Controller
B3
High pressure transmitter (liquid line)
B4
Low pressure transmitter (suction gas
line)
C1
Operating capacitor fan 1
C2
Operating capacitor fan 2
F2
Fuse rating 230 V
F3
Control circuit fuse
F5
High pressure switch
F6
Low pressure switch
K1
Main contactor
M1
Compressor
M1E
Oil heater
M1Y1
CRII SV1
M1Y2
CRII SV2
M2
Fan 1
M3
Fan 2
OLC-K1
Oil monitoring
Q1
Service switch
R3
Discharge gas temperature sensor
R4
Ambient temperature sensor
R5
Cold store temperature sensor
R8
Suction gas temperature sensor
SE-B1
Protection device
T1
Control transformer
V1
Fan control module
Tab. 5: Legend schematic wiring diagram ECOLITE