KB-206-1
27
Menu item
Function
Setting ex factory: 0 = substitute value deactivated
F2+F4⇒PAR⇒EMO⇒DO
Modbus: 16509
Substitute value for discharge gas temperature
-200.0 – 200.0°C
Setting ex factory: 100.0°C
F2+F4⇒PAR⇒EMO⇒FPE
Modbus: 16416
Signal for condenser fans speed in case of a sensor error
0.0 – 100.0%
Setting ex factory: 50.0%
The ECOLITE condensing unit includes emergency op-
eration modes and possibilities for manual intervention
for the case that defects or faults are active on elec-
tronic or electrical components. Further operation of the
condensing unit is only possible with slight restrictions
regarding its functionality or capacity until an adequate
spare part is available or other solutions are success-
fully implemented. Emergency operation modes must
not be used for continuous operation of the condensing
unit. The user must have sufficient technical expertise
to make decisions regarding the admissibility and the
effects of the functions. Only one of the emergency op-
eration modes may be active at any given time.
Monitoring of the application limits – menu ALr:
Menu item
Function
F2+F4⇒PAR⇒EMO⇒dHA
Modbus: 16426
Maximum condensing pressure (software high pressure switch)
0.0 – 100.0°C
Setting ex factory: 62.0°C
F2+F4⇒PAR⇒EMO⇒dHd
Modbus: 16427
Hysteresis at the max. condensing pressure (software high pressure switch)
0.0 – 10.0 K
Setting ex factory: 5.0 K
F2+F4⇒PAR⇒EMO⇒SLA
Modbus: 16428
Minimum suction pressure (software low pressure switch)
-60.0 – 50.0°C
Setting ex factory: -45.0°C
F2+F4⇒PAR⇒EMO⇒SLd
Modbus: 16429
Hysteresis at the min. suction pressure (software low pressure switch)
0.0 – 10.0 K
Setting ex factory: 5.0 K
F2+F4⇒PAR⇒EMO⇒dtA
Modbus: 16430
Maximum discharge gas temperature (software temperature switch)
0.0 – 150.0°C
Setting ex factory: 130.0°C
F2+F4⇒PAR⇒EMO⇒dtd
Modbus: 16431
Hysteresis at the max. discharge gas temperature (software temperature
switch)
0.0 – 20.0 K
Setting ex factory: 10.0 K
F2+F4⇒PAR⇒EMO⇒dtt
Modbus: 16432
Time delay when triggering discharge gas temperature errors
0 – 60 min
Setting ex factory: 5 min
F2+F4⇒PAR⇒EMO⇒OLt
Modbus: 16434
Limit for minimum overheating on suction side
0.0 – 5.0 K