Menu item
Function
F4⇒SCr⇒dS3
Modbus: 9016
(read only)
Operating hours counter of compressor
Number of days compressor has been operating
F4⇒SCr⇒HS3
Modbus: 9010
(read only)
Operating hours counter of compressor
Number of hours compressor has been operating
Display of the registered alarms (20 memory locations):
Menu item
Function
F4⇒HiSt⇒HYSP
Modbus: 9023
(read and write)
Alarm list memory locations
0 – 19 memory locations
0 = most recent memory location for last message
F4⇒HiSt⇒HYSC
Modbus: 9024
(read only)
Alarm list alarm numbers
F4⇒HiSt⇒HYSd
Modbus: 9024
(read only)
Alarm list date
Format DD.MM
F4⇒HiSt⇒HYSt
Modbus: 9026
(read only)
Alarm list time
Format HH:MM
F4⇒HiSt⇒HiSF
Modbus: 9027
(read only)
Alarm list number of stored error messages
The ECOLITE controller has an alarm memory for up to
20 error messages, which remain stored together with
a time stamp. The latest error message can be found in
the memory location 0.
Display and setting of date and time of the ECOLITE
controller:
Menu item
Function
F4⇒CLOC⇒HOUr
Modbus:
(read and write)
Setting of ECOLITE controller time – hour
0 – 24
F4⇒CLOC⇒Min
Modbus:
(read and write)
Setting of ECOLITE controller time – minute
0 – 59
F4⇒CLOC⇒dAY
Modbus:
(read and write)
Setting of ECOLITE controller date – day
0 – 31
F4⇒CLOC⇒MOnt
Setting of ECOLITE controller date – month