MK / MKT (E5) 03/2019
page 109/158
20.7 Water cooling (option)
Water cooling is a regularly available option for MK 56. For other chambers it is available via BINDER
Individual Customized Solutions.
The water cooling serves to cool the chamber instead of the air cooling and reduces the heat, which is
emitted to the ambient air during cooling operation.
MK 56, MK / MKT 115, 240:
The water cooling option allows to select between air cooling and water cool-
ing. The water cooling is turned on via the switch (3) in the lateral control panel. When it is turned off, the
air cooling is active.
MK / MKT 720:
With the water cooling option, the chamber always cools with the water cooling.
Retrofitting by the manufacturer is possible: The chamber must be returned to the BINDER factory for
installation.
Water connections
With the optional water cooling the chamber is supplied with cooling water via a freshwater pipe (max.
inlet temperature: 10 °C).
•
Connection of cooling water inlet: please refer to chap. 4.2
•
Connection of cooling water outlet: please refer to chap. 4.1
20.8 Object temperature display with flexible Pt 100 temperature sensor (option)
The object temperature display enables the determination of the actual temperature of the charging mate-
rial during the whole process. The object temperature is measured via a flexible Pt100 temperature sen-
sor and can be viewed on the controller display. The sensor top protective tube of the flexible Pt 100 can
be immersed into liquid substances.
Normal display with object temperature display
(sample values)
The object temperature data is given out together with the data of the temperature controller to the Ether-
net interface as a second measuring channel and can be documented by the APT-COM™ 4 Multi Man-
agement Software (option, chap. 20.1) developed by BINDER.
Technical data of the Pt 100 sensor:
•
Three-wire technique
•
Class B (DIN EN 60751)
•
Temperature range up to 320 °C /
608 °F
•
Stainless steel protective tube 45 mm /
1.78 in
length, material no. 1.4501
Содержание MK 115
Страница 129: ...MK MKT E5 03 2019 page 129 158 Heating up time MK 115 Cooling down time MK 115 Temp C Time min Time min Temp C ...
Страница 138: ...MK MKT E5 03 2019 page 138 158 24 12 Dimensions MK 56 dimensions mm ...
Страница 139: ...MK MKT E5 03 2019 page 139 158 MK MKT 115 dimensions mm ...
Страница 140: ...MK MKT E5 03 2019 page 140 158 MK 240 dimensions mm ...
Страница 141: ...MK MKT E5 03 2019 page 141 158 MKT 240 dimensions mm ...
Страница 142: ...MK MKT E5 03 2019 page 142 158 MK MKT 720 dimensions mm ...
Страница 143: ...MK MKT E5 03 2019 page 143 158 25 Certificates and declarations of conformity 25 1 EU Declaration of Conformity for MK ...
Страница 144: ...MK MKT E5 03 2019 page 144 158 ...
Страница 145: ...MK MKT E5 03 2019 page 145 158 ...
Страница 146: ...MK MKT E5 03 2019 page 146 158 25 2 EU Declaration of Conformity for MKT ...
Страница 147: ...MK MKT E5 03 2019 page 147 158 ...
Страница 148: ...MK MKT E5 03 2019 page 148 158 ...
Страница 150: ...MK MKT E5 03 2019 page 150 158 ...
Страница 151: ...MK MKT E5 03 2019 page 151 158 26 Product registration 26 1 Registering a BINDER chamber ...
Страница 159: ......