Installation, Operation and Maintenance Manual
MAN712 Rev. 9
June 2021
Configuration Parameters
Section 6: Configuration Parameters
55
Table of the Warnings (*)
Warning Type
Acronym
Description
Event Data Memory 90%
90%
内存容量
MEM90
It is active when the event data memory is not set as circular
(“Mem. Circular” = “No”) it reaches 90% of its capacity and if the
parameter “Memory 90%” is set as “On”.
Temperature
温度超范围
TEMP
It is active when the temperature is higher than +75 °C is lower
than -30 °C
Battery Maintenance Required
电池维护到期
MAINT
It is active if the present date is greater than or equal to the
“Next Batt. Ch.” parameter.
It is applicable only when the one or both the Battery Packs are
enabled (“V.Bat.Applied” is “Yes” ).
Position Transducer Problem
位置传感器异常
AI2_PO
It is active when some problem, dealing with the Position Sensor,
occurs (ex. Measured value > 20.6 mA or internal power supply
problem).
When the Position sensor is disabled, it is automatically cleared.
Interfaces Card Problem
接口卡通信异常
INTER
It is active when some problem, dealing with the communication
with the Interfaces Card, occurs
External Power Supply Default
默认供电电路异常
V_EX_D
It is active when “V. Ext Applied” is “Yes” and “V. Ext Status Def”
is “Bad”.
External Power Supply Auxiliary
备用供电电路异常
V_EX_A
It is active when “V. Ext Applied” is “Yes” and “V. Ext Status Aux”
is “Bad”
SVC1 Circuit Problem
电磁阀回路1异常
SVC1
It is active when SVC1 is set as SOV Control Output and “SVC1
Status” is “Bad”. See 5.2.8.1 for details.
SVC2 Circuit Problem
电磁阀回路2异常
SVC2
It is active when SVC2 is set as SOV Control Output and “SVC2
Status” is “Bad”. See 5.2.8.1 for details.
RL1 Circuit Problem
继电器回路1异常
RL1
It is active when RL1 is set as SOV Control Output and “RL1 Status”
is “Bad”. See 5.2.8.1 for details.
RL2 Circuit Problem
继电器回路2异常
RL2
It is active when RL2 is set as SOV Control Output and “RL2 Status”
is “Bad”. See 5.2.8.1 for details.
Battery Pack Default
默认电池组异常
BAT_D
It is active when “V.Bat.Applied” is “Yes” and the “V. Bat Status
Def” is “Bad”.
Battery Pack Auxiliary
备用电池组异常
BAT_A
It is active when “V.Bat.Applied” is “Yes”, “V.Bat.Dual” is “Yes” and
the “V. Bat Status Aux” is “Bad”.
Flash Process Card
Flash
设备异常
FL_P
It is active when the Flash memory of the Process Card
has problems.
MRAM Process Card
MRAM
设备异常
MR_P
It is active when the MRAM memory of the Process Card has
problems. This warning is not saved in the Warning List.
Flash Interfaces Card
Flash
接口卡异常
FL_I
It is active when the Flash memory of the Interfaces Card
has problems.
MRAM Interfaces Card
MRAM
接口卡异常
MR_I
It is active when the MRAM memory of the Interfaces Card
has problems.
Reset
重启
RESET
It is not a real warning; it is just logged in the “Warnings List” after
a reset (power cycle) of the ELBS-20.
Table 10.
NOTE:
(*):
The Active Alarms and Warnings are cleared after a power cycle of the device. After the power cycle if
the cause of the alarm or of the warning is still present, the alarm or warning will be again activated.