Section 6: Configuration Parameters
Configuration Parameters
42
Parameters of the “View Mode” Menu and the “Setup Mode” Menu
Parameter Name
Description
Range
Default
Value
R/W
(1)
Available
On (2)
Pres. Signal
(Pressure Signal)
压力传感器值
It must be set according to the
output of the Pressure Transducer
(Analog Input 1).
0 - 20 mA, 4 - 20 mA
4 - 20 mA
R/W
Local, Serial,
Modbus.
Pres. Min.
(Pressure Minimum)
压力传感器零点
For Biffi use only
0.0 bar
0.0 bar
R
Local, Serial,
Modbus.
Pres. Max.
(Pressure Maximum)
压力传感器量程
It must be set to the Pressure
Transducer Span (20 mA).
See Section 6.1 for the precision of the
Analog Input.
10.0-1000 bar
100.0 bar
R/W
Local, Serial,
Modbus.
Calibrate Pressure
压力传感器校准
For Biffi use only
-
-
-
Local, Serial,
Modbus.
Pos. Sens. En.
(Position Sensor
Enabled)
位置传感器
When it is set as “Yes”, the value of
the Position Sensor (Analog Input 2)
is sampled. When it is set as “No” the
shown position is “0.0%”.
Yes,
No
是,
否
No
否
R/W
Local, Serial,
Modbus.
Pos. Signal
(Position Signal)
位置传感器值
It must be set according to the output
of the Position Sensor.
0 - 20 mA, 4 - 20 mA
4 - 20 mA
R/W
Local, Serial,
Modbus.
Pos. Op. Mode
(Position Operating
Mode)
位置传感器作用模式
It determines in which way the AI2
(Position) input is read by the ELBS-20.
Normal: 20 mA = 100% (Fully Open),
0 or 4 mA(*) = 0% (Fully Close)
Reverse: 20 mA = 0% (Fully Close),
0 or 4 mA(*) = 100%
(Fully Open)
(*) It depends on “Pos. Signal” value
Normal,
Reverse
正向,
反向
Normal
正向
R/W
Local, Serial,
Modbus.
Start 20mA Calibration
(Calibrate Position
20 mA)
开始校准
20mA
It is used for accepting a tolerance of
the 20 mA value transmitted by the
Position Sensor.
For using this utility, it is necessary to
move the actuator for reaching the
position corresponding to the 20 mA
transmission (see Section 10.6).
This command does not work if
Operating Mode = SLEEP
Start
-
C
Local
Start 4 mA Calibration
(Calibrate Position
4 mA)
开始校准
4mA
It is used for accepting a tolerance of
the 4 mA value transmitted by the
Position Sensor.
For using this utility, it is necessary to
move the actuator for reaching the
position corresponding to the 4 mA
transmission (see Section 10.6).
It is useful only if
“Pos. Signal” = 4 - 20 mA.
DO NOT USE IT IF
“Pos. Signal” = 0 - 20 mA.
This command does not work if
Operating Mode = SLEEP.
Start
-
C
Local
Start 0mA Calibration
(Calibrate Position
0 mA)
开始校准
0 mA
It is used for accepting a tolerance of
the 0 mA value transmitted by the
Position Sensor.
For using this utility, it is necessary to
move the actuator for reaching the
position corresponding to the 0 mA
transmission (see Section 10.6).
It is useful only if “Pos. Signal” =
0 - 20 mA.
This command does not work if
Operating Mode = SLEEP.
Start
-
C
Local
Factory Settings
出厂设置
For Biffi use only
Start
-
C
Local