June 2021
Installation, Operation and Maintenance Manual
MAN712 Rev. 9
Section 6: Configuration Parameters
Configuration Parameters
38
Parameters of the “View Mode” Menu and the “Setup Mode” Menu
Parameter Name
Description
Range
Default
Value
R/W
(1)
Available
On (2)
SVC Enabled
电磁阀控制
Set as “SVC1”, SVC1 is used as SOV
Control Output.
Set as “Both”, SVC1 and SVC2 are used
as SOV Control Output. Set as “None”,
SVC1 and SVC2 are not used.
See Section 5.2.8 for details about the
SOVs Control Outputs.
RL1, Both,
None
电磁阀1控
制,
电磁阀1/2
控制,
无
SVC1
电磁阀1
控制
R/W
Local, Serial,
Modbus.
Relays Enabled
继电器控制
Set as “RL1”, RL1 is used as SOV Control
Output.
Set as “Both”, RL1 and RL2 are used as
SOV Control Output
Set as “None”, RL1 and RL2 are not
used.
See Section 5.2.8 for details about the
SOVs Control Outputs
RL1, Both,
None
继电器1控
制,
继电器1/2
控制,
无
None
无
R/W
Local, Serial,
Modbus.
Delay
延时启动
It is the delay of the starting of the
Safety Action. It is expressed in #
of Samples. See Sections 5.1.2.7,
5.1.2.6 and 5.1.3.
0 - 500
# of Samples
3
R/W
Local, Serial,
Modbus.
Duration
持续时间
It determines the time of command
of the dedicated SOV Control Outputs
(SVC and RL) to perform the Safety
Action. See Sections 5.1.2.7, 5.2.8 and
5.1.3 for details.
1-360 seconds
30
seconds
R/W
Local, Serial,
Modbus.
I.C. SVC En.
(Integrity Check SVC
Enabled)
电磁阀自动检测
If set as “Yes” the Automatic Integrity
Check is performed on the set/available
SVC Electrical Circuits (“SVC Enabled”).
The Automatic Integrity Check is
performed with a period defined by the
value of “I.C. SVC Time” and during the
Safety Action.
If it is set as “No” the Automatic
Integrity Check of the SVCs is disabled.
See Section 5.2.8.1 for details about
the Integrity Check.
Yes,
No
是,
否
Yes
是
R/W
Local, Serial,
Modbus.
I.C. SVC Time
(Integrity Check SVC
Time)
电磁阀检测周期
It determines the period of the
Automatic Integrity Check of the SVC
Electrical Circuits when “I.C. SVC En.” is
set as “Yes”.
If set as “0”, the Automatic Integrity of
the SVCs is performed only during the
Safety Action.
0 – 24 hours
8 hours
R/W
Local, Serial,
Modbus.
SVC1 Status
电磁阀1状态
It is the result of the Integrity Check of
the SVC1 Electrical Circuit.
It is applicable only if SVC1 is set as
SOV Control Output (“SVC Enabled”),
otherwise it is shown as “Ok”.
If SVC1 is set as SOV Control Output
and no Integrity Check is performed, it
is shown as “Ok”.
By setting “SVC Enabled = “None” or
“SVC1” it is set to “Ok”.
Ok,
Bad
正常,
异常
-
R
Local, Serial,
Modbus.
SVC2 Status
电磁阀2状态
It is the result of the Integrity Check of
the SVC2 Electrical Circuit.
It is applicable only if SVC2 is set as
SOV Control Output (“SVC Enabled”),
otherwise it is shown as “Ok”.
If SVC2 is set as SOV Control Output
and no Integrity Check is performed, it
is shown as “Ok”.
By setting “SVC Enabled = “None” or
“SVC1” it is set to “Ok”.
Ok,
Bad
正常,
异常
-
R
Local, Serial,
Modbus.