June 2021
Installation, Operation and Maintenance Manual
MAN712 Rev. 9
Section 8: Modbus RTU Interface
Modbus RTU Interface
84
Address Name
Range
Units
R/W
Description
(for full description see Section 6)
141
DO2 Function
0 - 16
-
RW
0 = SOV C., 1 = S.ACT., 2 = OFF, 3 = ARMED,
4 = ALARM, 5 = ACQ., 6 = WARN., 7 = V.E.KO,
8 = V.B.KO, 9 = B.MNT., 10 = S.A.DONE,
11 = SVC KO, 12 = RL KO, 13 = HEATER (*),
14 = EVENT2, 15 = EVENT4, 16 = EVENT6.
142
Reserved
0 - 16
-
R
-
143
DO2 Operating
Mode
0 - 1
-
RW
0 = Make, 1 = Break
144
DO2 Status
0 - 1
-
R
0 = Active, 1 = Not Active
145
DO3 Function
2 - 16
-
RW
2 = OFF, 3 = ARMED, 4 = ALARM, 5 = ACQ.,
6 = WARN., 7 = V.E.KO, 8 = V.B.KO,
9 = B.MNT., 10 = S.A.DONE, 11 = SVC KO,
12 = RL KO, 13 = HEATER (*), 14 = EVENT2,
15 = EVENT4, 16 = EVENT6.
146
Reserved
2 - 16
-
R
-
147
DO3 Operating
Mode
0 - 1
-
RW
0 = Make, 1 = Break
148
DO3 Status
0 - 1
-
R
0 = Active, 1 = Not Active
149
DO4 Function
2 - 16
-
RW
2 = OFF, 3 = ARMED, 4 = ALARM, 5 = ACQ.,
6 = WARN., 7 = V.E.KO, 8 = V.B.KO, 9 = B.MNT.,
10 = S.A.DONE, 11 = SVC KO, 12 = RL KO,
13 = HEATER (*), 14 = EVENT2, 15 = EVENT4,
16 = EVENT6.
150
Reserved
2 - 16
-
R
-
151
DO4 Operating
Mode
0 - 1
-
RW
0 = Make, 1 = Break
152
DO4 Status
0 - 1
-
R
0 = Active, 1 = Not Active
153
DO5 Function
2 - 16
-
RW
2 = OFF, 3 = ARMED, 4 = ALARM, 5 = ACQ.,
6 = WARN., 7 = V.E.KO, 8 = V.B.KO, 9 = B.MNT.,
10 = S.A.DONE, 11 = SVC KO, 12 = RL KO,
13 = HEATER (*), 14 = EVENT2, 15 = EVENT4,
16 = EVENT6.
154
Reserved
2 - 16
-
R
-
155
DO5 Operating
Mode
0 - 1
-
RW
0 = Make, 1 = Break
156
DO5 Status
0 - 1
-
R
0 = Active, 1 = Not Active
157
DO6 Function
2 - 16
-
RW
2 = OFF, 3 = ARMED, 4 = ALARM, 5 = ACQ.,
6 = WARN., 7 = V.E.KO, 8 = V.B.KO, 9 =
B.MNT.,
10 = S.A.DONE, 11 = SVC KO, 12 = RL KO,
13 = HEATER (*), 14 = EVENT2, 15 = EVENT4,
16 = EVENT6.
158
Reserved
2 - 16
-
R
-
159
DO6 Operating
Mode
0 - 1
-
RW
0 = Make, 1 = Break
160
DO6 Status
0 - 1
-
R
0 = Active, 1 = Not Active
161
DO7 Function
2 - 16
-
RW
2 = OFF, 3 = ARMED, 4 = ALARM, 5 = ACQ.,
6 = WARN., 7 = V.E.KO, 8 = V.B.KO, 9 = B.MNT.,
10 = S.A.DONE, 11 = SVC KO, 12 = RL KO,
13 = HEATER (*), 14 = EVENT2, 15 = EVENT4,
16 = EVENT6.
162
Reserved
2 - 16
-
R
-
163
DO7 Contacts
0 - 1
-
RW
0 = NC, 1 = NO
164
DO7 Operating
Mode
0 - 1
-
RW
0 = Make, 1 = Break
165
DO7 Status
0 - 1
-
R
0 = Active, 1 = Not Active