Configuration Parameters
Section 6: Configuration Parameters
41
Parameters of the “View Mode” Menu and the “Setup Mode” Menu
Parameter Name
Description
Range
Default
Value
R/W
(1)
Available
On (2)
Start Manual I.C. SVC
(Start Manual Integrity
Check SVC)
手动检测电磁阀
This command performs an Integrity
Check of the set/available SVC
Electrical Circuit.
See Section 5.2.8.1 for details about
the Integrity Check.
Start
-
C
Local, Serial,
Modbus.
I.C. RL En.
(Integrity Check RL
Enabled)
继电器自动检测
If set as “Yes” the Automatic Integrity
Check is performed on the set/available
RL Electrical Circuits (“Relays Enabled”).
The Automatic Integrity Check is
performed with a period defined by
the value of “I.C. RL Time” and during
the Safety Action.If it is set as “No” the
Automatic Integrity Check of the RLs
is disabled.
“RL1 Contacts” and “RL2 Contacts”
must be set correctly.
See Section 5.2.8.1 for details about
the Integrity Check.
Yes,
No
是,
否
No
否
R/W
Local, Serial,
Modbus.
I.C. RL Time
(Coils Test RL Time)
继电器检测周期
It determines the period of the
Automatic Integrity Check of the RL
Electrical Circuits when “I.C. RL En.” is
set as “Yes”.
If set as “0”, the Automatic Integrity of
the RLs is performed only during the
Safety Action
0 – 24 hours
8 hours
R/W
Local, Serial,
Modbus.
RL1 Contacts
继电器1触点
It indicates which contact of the RL1 is
used (NC = Normally Closed or
NO = Normally Open).
It deals with the Integrity Check
execution and if it is not set correctly,
the result of the Integrity Check of the
RL1 Electrical Circuit has no sense.
See Section 5.2.8.1 for details about
the Integrity Check.
NC,
NO
常闭,
常开
NO
常开
R
Local, Serial,
Modbus.
RL2 Contacts
继电器2触点
It indicates which contact of the RL2 is
used (NC = Normally Closed or
NO = Normally Open).
It deals with the Integrity Check
execution and if it is not set correctly,
the result of the Integrity Check of the
RL2 Electrical Circuit has no sense.
See Section 5.2.8.1 for details about
the Integrity Check.
NC,
NO
常闭,
常开
NO
常开
R
Local, Serial,
Modbus.
RL1 Status
继电器1状态
It is the result of the Integrity Check of
the RL1 Electrical Circuit.
It is applicable only if RL1 is set as SOV
Control Output (“Relays Enabled”),
otherwise it is shown as “Ok”.
If RL1 is set as SOV Control Output and
no integrity Check is performed, it is
shown as “Ok”.
By setting “Relays Enabled = “None” it
is set to “Ok”.
Ok,
Bad
正常,
异常
-
R
Local, Serial,
Modbus.
RL2 Status
继电器2状态
It is the result of the COILS TEST of the
RL2 Electrical Circuit.
It is applicable only if RL2 is set as SOV
Control Output (“Relays Enabled”),
otherwise it is shown as “Ok”.
If RL2 is set as SOV Control Output and
no Integrity Check is performed, it is
shown as “Ok”.
By setting “Relays Enabled” “None” or
“RL1” it is set to “Ok”.
Ok,
Bad
正常,
异常
-
R
Local, Serial,
Modbus.
Start Manual I.C. RL
(Start Manual Integrity
Check RL)
手动检测继电器回路
This command performs an Integrity
Check of the set/available RL Electrical
Circuit.
“RL1 Contacts” and “RL2 Contacts”
must be set correctly.
See Section 5.2.8.1 for details about
the Integrity Check.
Start
-
C
Local, Serial,
Modbus.