June 2021
Installation, Operation and Maintenance Manual
MAN712 Rev. 9
Section 8: Modbus RTU Interface
Modbus RTU Interface
86
Address Name
Range
Units
R/W
Description
(for full description see Section 6)
211
Modbus Baud Rate
0 - 6
-
R
0= 600 bps, 1= 1200 bps, 2 = 2400 bps,
3 = 4800 bps, 4 = 9600 bps, 5 = 19200 bps,
6 = 38400 bps
212
Modbus Parity
0 - 2
-
R
0 = Odd, 1 = Even, 2 = None
213
Modbus
Termination Active
0 - 1
-
R
0 = No, 1 = Yes
214
Reserved
0 - 65535
-
R
-
215
Reserved
0 - 65535
-
R
-
216
Reserved
0 - 65535
-
R
-
217
Reserved
0 - 65535
-
R
-
DI2 Active If
0 - 1
-
RW
0 = Absent, 1 = Present
218
Reserved
0 - 65535
-
R
DI2 Status
0 - 1
-
R
0 = Low, 1 = High
219
Reserved
0 - 65535
-
R
-
Reserved
0 - 7
-
R
-
220
Last Battery
Maintenance Date
-
-
R
dd/mm (BCD format)
221
Last Battery
Maintenance Date
-
-
R
yyyy (BCD format)
222
Next Battery
Maintenance Date
-
-
R
dd/mm (BCD format)
223
Next Battery
Maintenance Date
-
-
R
yyyy (BCD format)
224
Battery
Maintenance
Period
1 - 5
Years
RW
-
225
Reserved
0 - 1
-
R
-
226
Reserved
2 - 2000
R
-
227
Reserved
0 - 1
-
R
-
228
Start Test Safety
Action
0 - 1
-
RW
0 = No, 1 = Start
229
Device Type
0 - 1
-
R
0 = ELBS-20, 1 = ELBS-30
230
Manufacturer
0
-
R
0 = Biffi
231
Serial Number
ASCII
-
R
Serial Number (MSB)
232
Serial Number
ASCII
-
R
-
233
Serial Number
ASCII
-
R
-
234
Serial Number
ASCII
-
R
-
235
Serial Number
ASCII
-
R
-
236
Serial Number
ASCII
-
R
-
237
Serial Number
ASCII
-
R
-
238
Serial Number
ASCII
-
R
Serial Number (LSB)
239
FW Interface
ASCII
-
R
FW Interfaces Card (MSB)
240
FW Interface
ASCII
-
R
FW
241
FW Interface
ASCII
-
R
FW
242
FW Interface
ASCII
-
R
FW Interfaces Card (LSB)
243
FW Process
ASCII
-
R
FW Process Card (MSB)
244
FW Process
ASCII
-
R
FW
245
FW Process
ASCII
-
R
FW
246
FW Process
ASCII
-
R
FW Process Card (LSB)
247
Tag Name
ASCII
-
R
Tag Name (MSB)
248
Tag Name
ASCII
-
R
-
249
Tag Name
ASCII
-
R
-
250
Tag Name
ASCII
-
R
-