RS-485 COMMUNICATION PROTOCOL FOR SITE MASTER SP
Read all safety instructions and notes before applying power to the Site Master.
NOTES FOR COMMUNICATION WIRING DIAGRAM
1.
All wiring must be installed and used in accordance with the national electrical code (NFPA #70, Automotive and marine service code
NFPA #30A), state, and local electrical codes.
2.
All wiring gauge is minimum required, stranded wire with THHN insulation must be used. Do not reuse old wire from an existing
installation.
3.
Do not use PVC conduit. Use only rigid metal conduit.
4.
Field connection =
P4229
Sheet 2
Rev B