Menu mode: Operation and setting
75
ATICS-DIO_D00080_01_M_XXEN/04.2015
7.3.4.6
Settings menu 6: Datalogger
Data logger ATICS-2-DIO
The settings for the data loggers of the device are adjusted on this menu. These data loggers (see
"Menu 3: History/Logger" on page 64) display the history of the measured values:
Data logger ATICS-4-DIO
The settings for the data loggers of the device are adjusted on this menu. These data loggers (see
"Menu 3: History/Logger" on page 64) display the history of the measured values:
Do not set inputs with contradictory functions simultaneously!
For each of the four digital inputs a function can be set. This function is only ac-
tivated when the input is activated.
Example:
Digital input 1 is set to "1"
Digital input 2 is set to "2"
Digital input 3 is set to "0"
Digital input 4 is set to "M/A"
When the digital inputs 1 and 4 are activated, the ATICS® switches to switch po-
sition "I". When the digital inputs 2 and 3 are also activated, it will have no effect.
The function of the input set first has priority.
If the digital input 1 is no longer activated, the function of the digital input with
the next number up will be activated.
Data logger
Meaning
1. Line 1
Line 1: Measured value mains voltage phase to neutral conductor N
2. Line 2
Line 2: Measured value mains voltage phase to neutral conductor N
3. Position
Switch position of the changeover switch
4. I(3)
Load current downstream of the transfer switching device
Data logger
Meaning
1. U1(1-N)
Line 1: Measured value mains voltage phase L1 to neutral conductor N
2. U1(2-N)
Line 1: Measured value mains voltage phase L2 to neutral conductor N
3. U1(3-N)
Line 1: Measured value mains voltage phase L3 to neutral conductor N
4. U2(1-N)
Line 2: Measured value mains voltage phase L1 to neutral conductor N
5. U2(2-N)
Line 2: Measured value mains voltage phase L2 to neutral conductor N
6. U2(3-N)
Line 2: Measured value mains voltage phase L3 to neutral conductor N
7. Position:1
Switch position of the changeover switch
8. I(1)
Load current downstream of the transfer switching device on phase L1
9. I(2)
Load current downstream of the transfer switching device on phase L2
Содержание ATICS-2-63A-DIO
Страница 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...
Страница 102: ...Data 102 ATICS DIO_D00080_01_M_XXEN 04 2015...