Menu mode: Operation and setting
64
ATICS-DIO_D00080_01_M_XXEN/04.2015
7.3.3
Menu 3: History/Logger
The device saves the history of alarm messages, measured values, settings, tests and servicing activ-
ities in different memories (logger).
See the technical specifications for information about the maximum number of events which can be
saved. Once the maximum number of events which can be saved is reached, the latest event is writ-
ten over the oldest entry (Entry 1).
Menu item
Function
Exit
Exit "History/Logger" menu; go up one menu level
1. History
The "History" menu provides information about alarm messages and tests which
have been performed. It also indicates whether an alarm is still pending or when
it was acknowledged by pressing the "mute" button on a TM… alarm indicator
and operator panel or an MK… alarm indicator and test combination.
2. Data logger
Displays the history of measured values: Voltage Line 1, Voltage Line 2, switch
position of the changeover switch, load current in the TN system downstream of
the transfer switching device I(3).
3. Config.logger
Shows the history of all parameter changes, their origin, modified settings and
the date of the change (can only be displayed on the device):
Internal
change was carried out in the "Settings" menu on the device.
External
change was carried out via an external device (e.g. BMS-Ethernet-
Gateway COM460IP).
Auto
Automatic change, in response to a change of another parameter.
Example see "Settings menu 4: Relay" on page 71.
4. Test data logger
Displays the history of the tests carried out: date, time and changeover period.
Also refer to "Time diagram: Changeover between the preferred and redundant
line" on page 16.
5. Service logger
Displays the history of the service activities carried out: Date, time and service
codes. Meaning of the displayed service code: see table "Messages with error
code or service code" on page 82.
Содержание ATICS-2-63A-DIO
Страница 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...