![Bender ATICS-2-63A-DIO Скачать руководство пользователя страница 71](http://html1.mh-extra.com/html/bender/atics-2-63a-dio/atics-2-63a-dio_manual_2731773071.webp)
Menu mode: Operation and setting
71
ATICS-DIO_D00080_01_M_XXEN/04.2015
7.3.4.4
Settings menu 4: Relay
On this menu, you can adjust settings for the mode of operation and function of the relay outputs
(alarm relays). For each relay the function can be set: alarm message, operational status message,
generator start. This setting affects the action of the following menus.
If "Alarm" is set and then "Line 1:on" is selected, the relay switches when Line 1 has failed. If "Enable"
is set and then "Line 1:on" is selected, the relay switches when Line 1 is in operation. The setting "on"
can be selected for several menus simultaneously. The relay switches when at least one of the con-
ditions is met.
If "GenSt" is set for alarm relay 1, the operating mode will always be set to "N/C-T" on. The other set-
tings on the "Relay 1" menu are disabled. The alarm message "Failure Line 2" is suppressed.
Select a relay as follows:
1. Use the arrow button "
" to set the alarm relay. Press "
↵
".
2. Use the arrow buttons to select an alarm relay (e.g. Relay 2) or all the four alarm relays
(Relay 1…4). Press "
↵
" to confirm your selection.
Adjusting the settings:
If the setting "L-Gen" is selected on the "Changeover -> System" settings menu,
the alarm relay is permanently set to:
- 1. Mode:
GenSt
- 2. Relay mode:
N/C-T
- Menu items 4 … 9
disabled
Menu
Meaning
Exit
Exit settings menu "Relays"; go up one menu level
1. Mode
ALARM
Relay switches if at least one of the following menus 3…6 is set
to "on" and the associated alarm message appears.
Enable
Relay switches if at least one of the following menus 3…6 is set
to "on" and the associated alarm message does
not
appear
(operational status message)
GenSt
Relay is used as a generator start relay
(alarm relay 1 only)
Relay: 2
Exit
1.Mode: Alarm
2.Relay mode:N/C-T
Relay: 1..4
Exit
1.Mode: Alarm
2.Relay mode:N/C-T
Setting one relay
Setting all the four relays
Содержание ATICS-2-63A-DIO
Страница 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...
Страница 102: ...Data 102 ATICS DIO_D00080_01_M_XXEN 04 2015...