Selecting a data logger:
1. Use the "
" arrow button to go to the data logger setting. Press "
↵
".
2. Use the arrow buttons to select one data logger (1, 2, …) or all data loggers (ATICS-2-DIO: 1…4,
ATICS-4-DIO: 1…11). Press "
↵
" to confirm your selection.
Adjusting settings and deleting data loggers:
10. I(3)
Load current downstream of the transfer switching device on phase L3
11. I(N)
Load current downstream of the transfer switching device on neutral con-
ductor N
Risk of premature wear of the memory chip
The service life of the 300 memory locations of the EEPROM memory is limited to
about 100 000 memory accesses. If one change to a measured value is saved
every second, the end of the service life of the EEPROM is reached after one year.
If one change to the measured value is saved every minute, then the service life is
increased by about 57 years. Select the settings in the "Datalogger -> "Modific."
settings menu in a way that frequent saving over longer periods of time can be
avoided.
To protect the memory module, a minimum limit threshold of 10 A for the load
current is incorporated in the data logger for the TN system and a minimum limit
threshold of 20 % in the data logger for the IT system. Values below this limit
threshold are only stored once. A new measured value will be stored in the mem-
ory chip only when this limit threshold is exceeded.
Menu
Meaning
Exit
Exit settings menu "Datalogger"; go up one menu level
1. Modific.:
Once the measured value is changed according to the set % value, a new meas-
ured value is saved to the data logger.
Setting range:
0 … 100 %
Resolution of setting:
1 %
Data logger
Meaning
No.:4 U2(1-N)
Exit
1.Modific.: 10.00 %
2.Overwrite: yes
No.:1..11
Exit
1.Modific.: 10.00 %
2.Overwrite: yes
Set one
data logger
Set all data loggers
Содержание ATICS-2-63A-DIO
Страница 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...
Страница 102: ...Data 102 ATICS DIO_D00080_01_M_XXEN 04 2015...