Menu mode: Operation and setting
74
ATICS-DIO_D00080_01_M_XXEN/04.2015
1. Mode
Note: A parameter change can result in an immediate changeover.
off
Digital input switched off
M/A
Manual/Automatic.
Manual mode means that automatic changeover can no longer
take place.
Bypass
Alarm "Manual mode", but test changeover possible
no2->1
Switching-back interlocking function. After changing over to
Line 2, the changeover switch remains in this switch position. It
waits there even when Line 1 returns. It does not switch back to
Line 1 until the digital input is no longer set, Line 2 fails or the
reset button is pressed. The display shows the operational sta-
tus message "SwitchBackLock".
1<->2
Changing the preferred line
TEST
A test changeover is carried out. In generator mode, the gener-
ator start relay is also switched. The test is terminated when the
output is reset.
1
Switch to position 1*
0
Switch to position 0*
2
Switch to position 2*
* Requirement: another digital input is set to "M/A".
ALARM
Generates a "Digital input alarm".
An alarm relay of an external Isometer can be connected here.
The alarm message appears on the display and is passed on via
the BMS bus. The alarm relay switches when adjusted accord-
ingly. The alarm message has no effect on the changeover
function.
R-OPL
Generates an alarm "Insulation fault, operating theatre lights".
Other functions as for the setting "ALARM".
2. Resp. val.
0V
At 0 V input is set. Set function is carried out.
24V
At 24 V input is set. Set function is carried out.
3. t(on)
Response delay:
100 ms…100 s
Resolution of setting:
starting at 50 ms
4. t(off )
Delay on release:
100 ms…100 s
Resolution of setting:
starting at 50 ms
The common alarm for the digital inputs 2…4 is signalled on channel 12 of the
BMS bus. If one of these digital inputs is set to "ALARM" and activated, an alarm
will be outputted on channel 12. It cannot be recognised which digital input has
tripped. Only one alarm will be outputted. Priority is given to the alarm of the
digital input with the lowest number.
Example:
Digital input 2 is set to "ALARM" and activated.
Digital input 3 is set to "R-OPL" and activated.
In this case, only the message of digital input 2 (ALARM) will be indicated on
channel 12 of the BMS bus. Only when digital input 2 is no longer activated, the
message of digital input 3 will be indicated (R-OPL).
Menu
Meaning
Содержание ATICS-2-63A-DIO
Страница 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...
Страница 102: ...Data 102 ATICS DIO_D00080_01_M_XXEN 04 2015...