Menu mode: Operation and setting
78
ATICS-DIO_D00080_01_M_XXEN/04.2015
7.3.4.9
Settings menu 9: Clock
This menu is used to set the date format, date and time for indication on the "History/Logger" menu.
The time setting is synchronised via the BMS bus. The device with address 1 (MK800, MK2430 or
TM…) synchronises all other devices every hour.
The time setting for the ATICS® is required in that rare case when no BMS bus is used. In this case, the
ATICS® shows the fault message "No Master". The date format, date and time can be set. These set-
tings remain stored for approx. eight hours following a supply interruption. The date and time will
then be reset to the factory settings (01.01.2010, 00:00:00).
7.3.4.10 Settings menu 10: Password
The device has two separate passwords for the "Settings" menu and the "TEST" menu.
4. Failure monitoring
on
Alarm, if no communication with BMS master is detected.
off
The presence of a BMS master is not monitored. This setting is
required when the ATICS® is used as a "Stand-alone" device
without BMS master.
Menu
Meaning
Exit
Exit settings menu "Clock"; go up one menu level
1. Format
d.m.y
German format (day.month.year)
m-d-y
American format
2. Date
Setting the date (e.g. dd.mm.yyyy)
3. Time
Setting the time (hours and minutes)
Menu
Meaning
Exit
Exit settings menu "Password"; go up one menu level
1. Settings
Change the password for the "Settings" menu, switch the password "on/off" Fac-
tory setting:
Password: 000
Status: off
2. TEST
Change the password for the "TEST" menu, switch the password on/off. Factory
setting
Password: 000
Status: off
Menu
Meaning
When this setting is selected, the conditions for func-
tional safety (SIL2) are no longer met.
In the event of a power failure of more than eight hours,
the time and date will be reset to the factory settings. If the
"Clock" setting is not corrected, all functions depending
on this setting (history memory, logger, test interval, serv-
ice interval...) will lead to unusable results.
DANGER
CAUTION
Содержание ATICS-2-63A-DIO
Страница 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...