Installation and connection
29
ATICS-DIO_D00080_01_M_XXEN/04.2015
Terminals for ATICS-2-DIO connection
Key
1L, 1N
Connection for Line 1 (input line)
2L, 2N
Connection for Line 2 (input line)
L, N
Connection for Line 3 (output line)
l, k
Connection measuring current transformer T3 (STW3) for monitoring the load
current downstream the transfer switching device (short-circuit monitoring)
GND, En/Ex
Terminals must not be used. These terminals are solely intended for future
extensions (12 V).
IN1/GND, IN1
Digital input, configurable (see "Settings menu 5: Digital Input" on page 73)
NC
Not used
24, 34, 44, 21
3 alarm relays (1 N/O contact each), 21 = common connection for the three
alarm relays
IN2, IN3, IN4, IN2-4 GND
3 digital inputs
A, B
BMS bus connection
14, 12, 11
Alarm relay, programmable function