6.6
Short-term power failure
Malfunction image
Close valves V1 / V2.
The current supply is interrupted.
No alarm is displayed.
Cause
Measure
Interruption of the voltage supply.
The valves close automatically.
When the power is restored, the time of
approx. 5 hours via the K1T (see E-plan
page 6) expires again.
At a reactor temperature between
+ 130 °C and + 150 °C, the RESET function
of K1T can be used (refer to Chapter 6.10).
Exceeding the permissible voltage range.
This will trigger the fuses and interrupt the
voltage supply.
The valves close automatically.
When the power is restored, the time of
approx. 5 hours via the K1T (see E-plan
page 6) expires again.
At a reactor temperature between
+ 130 °C and + 150 °C, the RESET function
of K1T can be used (refer to Chapter 6.10).