User Guide Revision 1.12
59
P8-17
Assist Pump Start Speed
P8-18
P1-01
0
Hz / RPM
H2 drive upper speed Staging threshold. When the drive output increases beyond this threshold the next Staging pump is switch on.
The Pump staging settle time must then expire before additional staging pumps can be brought on or off line. Priority for Staging
pump switch on is always given to the pump with lowest run time accumulated.
P8-18
Assist Pump Stop Speed
0
P8-17
0
Hz / RPM
H2 drive lower speed Staging threshold. When the drive output decreases below this threshold one of the Staging pumps currently
operating is switch off. The Pump staging settle time must then expire before additional staging pumps can be brought on or off line.
Priority for Staging pump switch off is always given to the pump with highest run time accumulated.
P8-19
Pump Settling Time
10
600
10
Secs
Parameter sets a time delay for pump staging whereby, following switch in or switch out of a staging pump, further pumps are not
permitted to be switched in or out until this time period has elapsed. This parameter should be set to allow adequate settle time
between staging pump transitions.
P8-20
Pump Master Clock Reset
0
1
0
-
Master drive in pump staging monitors and maintains duty run times for all available staging pumps. All clocks are available to view in
P0-20. P8-20 provides the master reset to all run time clocks used for Pump Staging Function (all clocks set to 0).
Note:
For full detail of Pump Staging function configuration see section 7.1 and 7.2, or contact your local drive distributor
-
11.8.
Parameter Group 9 – Advance drive control logic configuration
Menu group 9 parameters are detailed in the following Reference Table. They can be accessed through the drive keypad by setting advanced
security level access (P1-14 = 201) or through the OptiTools Studio software suite. Care should be taken in adjusting these parameters. Please
contact your local distributor for further assistance.
P9-01
Enable Input Source
Defines the source of the signal to be used for the Enable input
P9-02
Fast Stop Input Source
Defines the source of the signal to be used for the Fast Stop input
P9-03
Forward Run Input Source
Defines the source of the signal to be used for the Forward Run input
P9-04
Reverse Run Input Source
Defines the source of the signal to be used for the Reverse Run input
P9-05
Latch Function Enable
Latch function enable control for the run signals (P9-03 and P9-04)
P9-06
Reverse Enable Source
Defines the source of the signal to be used for Reverse run direction control
P9-07
Reset Input Source
Defines the source of the signal to be used for the Reset input
P9-08
External Trip Input Source
Defines the source of the signal to be used for the External trip input
P9-09
Terminal Control Override Source
Defines the source of the signal to be used for the terminal control override
P9-10
Speed Source 1
Defines the Reference Value used for Speed Source 1
P9-11
Speed Source 2
Defines the Reference Value used for Speed Source 2
P9-12
Speed Source 3
Defines the Reference Value used for Speed Source 3
P9-13
Speed Source 4
Defines the Reference Value used for Speed Source 4
P9-14
Speed Source 5
Defines the Reference Value used for Speed Source 5
P9-15
Speed Source 6
Defines the Reference Value used for Speed Source 6
P9-16
Speed Source 7
Defines the Reference Value used for Speed Source 7
P9-17
Speed Source 8
Defines the Reference Value used for Speed Source 8
P9-18
Speed Select Input 0
Speed multiplex input 0
P9-19
Speed Select Input 1
Speed multiplex input 1
P9-20
Speed Select Input 2
Speed multiplex input 2
P9-21
Preset Speed Select Input 0
Preset speed selection multiplex input 0
P9-22
Preset Speed Select Input 1
Preset speed selection multiplex input 1
P9-23
Preset Speed Select Input 2
Preset speed selection multiplex input 2
P9-28
Remote Up Button Input Source
Defines the source of the signal to be used as the Remote UP button
P9-29
Remote Down Button Input Source
Defines the source of the signal to be used as the Remote DOWN button
P9-32
Fire mode trigger input selection
Defines the source of the signal to be used for the Fire mode input
P9-33
Analog Output 1 Control Source
This parameter specifies the relay output 1 control source
P9-34
Analog Output 2 Control Source
This parameter specifies the relay output 2 control source
P9-35
Relay 1 Control Source
This parameter specifies the relay output 1 control source
P9-36
Relay 2 Control Source
This parameter specifies the relay output 2 control source
P9-37
Scaling Source Control
This parameter specifies the scaling control source
P9-38
PID Reference Source Control
This parameter specifies the PID reference source
P9-39
PID Feedback Source Control
This parameter specifies the PID feedback source
P9-41
Relay outputs 3, 4, 5 Function Select
Defines the function of Extended I/O relay outputs 3, 4 and 5
P9-42
Clean Trigger Input (Edge)
Defines the source of the signal to be used for the pump clean enable input
P9-43
Bypass Trigger Input
Defines the source of the signal to be used for the Bypass function enable input
P9-44
PID 2nd Digital Reference Select Input
Defines the source of the signal to be used for selecting the 2nd digital reference for PID