3.12.
Gland Plate and Lock Off
The use of a suitable gland system is required to maintain the appropriate IP / Nema rating. Cable entry holes will need to be drilled to suit
this system. Some guidelines sizes are defined below:
Please take care when drilling to avoid leaving any particles within the product.
Cable Gland recommended Hole Sizes & types:
Min Gland Rating
Hole Size
Imperial
Metric
Size 2
IP66
3 x 22mm
3 PG13.5
3 x M20
Size 3
IP66
1 x 22mm and 2 x 28mm
1 PG13.5 and 2 PG16
1 x M20 and 2 x M25
UL rated ingress protection ("Type " ) is only met when cables are installed using a UL recognized bushing or fitting for a flexible-
conduit system which meets the required level of protection ("Type")
For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC
Not intended for rigid conduit system
Power Isolator Lock Off – IP66 with Built in Isolator Option
On the switched models the main power isolator switch can be locked in the ‘Off’ position using a 20mm standard shackle padlock (not
supplied).
IP66 / Nema 12 Unit Lock Off
IP66 / Nema 4X Unit Lock Off