M-3520 Instruction Book
6–30
59G Neutral Overvoltage
VOLTAGE INPUTS:
See Below
CURRENT INPUTS:
None
TEST SETTINGS:
Pickup
P
Volts
(5 to 180)
Time Delay
D
Cycles
(1 to 8160)
Programmed Outputs
Z
Output
(1 to 8)
Functions 27G, 79
Disable
1.
Disable functions as shown. Refer to Section 3.2, Configure Relay Data, for procedure.
2.
Confirm settings to be tested.
3.
Connect voltage input to terminal numbers 41 and 42.
4.
Pickup Test
: Hold the
TARGET RESET
button in and slowly increase the input Neutral voltage until
59G NEUTRL OVERVOLTAGE
LED illuminates or the pickup indicator operates on the computer
target screen. The level should be equal to
P
volts ±0.5 V or 5%. Release the
TARGET RESET
button and decrease the input voltage and the
OUTPUT
LED’s will extinguish. Press
TARGET
RESET
button to remove targets.
5.
Time Test
: With output contacts being connected to the timer, apply
P
+1 volts and start timing. The
contacts will close after
D
cycles within –1 to +3 cycles or 1%.
6.
If testing is complete, enable any functions disabled for this test. If further testing is desired, check
the proper functions to disable for the next test and continue from this point.
Содержание M-3520
Страница 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Страница 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Страница 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Страница 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Страница 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Страница 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...