2–23
Application - 2
50 Instantaneous Overcurrent, 3-Phase
The Instantaneous Phase (50) functions provide
fast tripping times for high fault currents. The settings
for 50 should be chosen such that they will not
respond to faults on the adjacent system.
Save
Cancel
@ : WARNING, Function DISABLED until output selected!
(50) - INSTANTANEOUS PHASE OVERCURRENT
1.0 Amp
240.0 Amps
#1
OUTPUT
8
7
6
5
4
3
2
1
FL
6
5
4
3
2
1
Blocking Input
@
Pickup:
Figure 2-14
M-3822 IPScom
®
for Windows™ Instantaneous Phase Overcurrent (50) Setpoint
Ranges
Path
: Relay Menu/Setup/Setpoints/(50) Instantaneous Phase Overcurrent
COMMAND BUTTONS
Save
Saves all information to the relay.
Cancel
Returns the user to the previous window; any changes to the displayed information are lost.
If this function is enabled, the following setting is applicable:
50 PICKUP
________ Amps