–6–
M-3520 Intertie Protection Relay
STANDARD FUNCTIONS (
cont.)
Device
Setpoint
Number
Function
Ranges
Increment
Accuracy
†
Reconnect Enable Time Delay
Reconnect Enable Time Delay
Reconnect Enable Time Delay
Reconnect Enable Time Delay
Reconnect Enable Time Delay
Reconnect Delay
2 to 65500 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
Reconnect timer starts when all outputs designated as trip outputs dropout.
Frequency
Frequency
Frequency
Frequency
Frequency
Pickup #1, #2, #3, #4
50.00 to 67.00 Hz
0.01 Hz
&
0.02 Hz
40.00 to 57.00 Hz*
Time Delay #1,#2, #3, #4 2 to 65,500 Cycles
1 Cycle
–2 to +3 Cycles or
&
1%
The pickup accuracy applies to 60 Hz models at a range of 57 to 63 Hz, and to 50 Hz models at a range
of 47 to 53 Hz. Beyond these ranges, the accuracy is
&
0.1 Hz.
*This range applies to 50 Hz nominal frequency models.
†
Select the greater of these accuracy values.
Values in parentheses apply to 1 Amp CT secondary rating.