
2–24
M-3520 Instruction Book
50G Instantaneous Overcurrent, Neutral
The Instantaneous Neutral Overcurrent (50G) function
provides fast tripping times for high fault currents.
The settings for 50G should be chosen such that
they will not respond to faults on the adjacent system.
Save
Cancel
@ : WARNING, Function DISABLED until output selected!
(50G) - INSTANTANEOUS NEUTRAL OVERCURRENT
#1
OUTPUT
8
7
6
5
4
3
2
1
FL
6
5
4
3
2
1
Blocking Input
@
Ground Directional Element
Enable
Disable
Pickup:
.5 Amp
240.0 Amps
Figure 2-15
M-3822 IPScom
®
for Windows™ Instantaneous Neutral Overcurrent (50G) Setpoint
Ranges
Path
: Relay Menu/Setup/Setpoints/(50G) Instantaneous Neutral Overcurrent
COMMAND BUTTONS
Save
Saves all information to the relay.
Cancel
Returns the user to the previous window; any changes to the displayed information are lost.
If this function is enabled, the following settings are applicable:
50G PICKUP
________ Amps
DIRECTIONAL ELEMENT
disable ENABLE
Pickup setting.
50G may be directionally controlled. See 67N function for
maximum sensitivity angle and polarization setup.
Содержание M-3520
Страница 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Страница 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Страница 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Страница 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Страница 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Страница 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...