2–49
Application - 2
2.7
IRIG-B Time Sync
The M-3520 Intertie Protection Relay has the ability
to accept either a modulated or demodulated IRIG-B
signal. The modulated signal is connected using the
rear panel BNC connector, and is the default
configuration.
A demodulated TTL level signal may also be used
by connecting the signal source to two unused pins
on the rear panel COM2 RS-232 connector (see
table B-1). For demodulated operation, several
jumpers need to be reconfigured (see Section 5.5,
Circuit Board Switches and Jumpers).
When valid IRIG-B time information is received, the
TIME SYNC LED is illuminated, and the hour,
minute, and seconds of the on-board real-time clock
(RTC) are corrected to the new IRIG-B time at five
(5) minutes before the hour. Extended time
information, accurate to 1 ms, is appended to all
oscillograph and target time tags.
2.6
Target History Recorder
Designated tripping output. In this sample, O1–O7
are trip outputs, and o8 is used for reconnect.
The 32 most recent target events are stored in the
unit’s memory. A target is triggered whenever an
output (designated as a trip output) operates.
The setup of the Target History Recorder includes the following setting:
TRIGGER OUTPUTS
o8 O7 O6 O5 O4 O3 O2 O1
Содержание M-3520
Страница 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Страница 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Страница 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Страница 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Страница 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Страница 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...