2–14
M-3520 Instruction Book
79 SUPERVISE 25
disable ENABLE
25 PHASE LIMIT
________
Degrees
25 UPPER VOLT LIMIT
________ Volts
25 LOWER VOLT LIMIT
________ Volts
25 SYNC CHECK DELAY
________ Cycles
25 DELTA VOLT
disable ENABLE
25 DELTA VOLT LIMIT
________ Volts
25 DELTA FREQUENCY
disable ENABLE
25 DELTA FREQUENCY LIMIT
________ Hz
25 DEAD VOLT LIMIT
________ Volts
25 DEAD V1
disable ENABLE
25 DEAD V2
disable ENABLE
25 DEAD V1 & V2
DISABLE enable
If enabled, 79 timer will control 25 function.
Phase angle setting.
Upper voltage limit for voltage acceptance.
Lower voltage limit for voltage acceptance.
Sync check time delay.
Delta voltage element.
Delta voltage setting.
Delta frequency element.
Delta frequency setting.
Voltage less than this setting is defined as “DEAD”; above
this setting as “HOT”.
Enables Dead V1/Hot V2 setting.
Enables Hot V1/Dead V2 setting.
Enables Dead V1/Dead V2 closing.
If this function is enabled, the following settings are applicable: