–5–
M-3520 Intertie Protection Relay
STANDARD FUNCTIONS (
cont.)
Device
Setpoint
Number
Function
Ranges
Increment
Accuracy
†
VT Fuse–Loss Detection
VT Fuse–Loss Detection
VT Fuse–Loss Detection
VT Fuse–Loss Detection
VT Fuse–Loss Detection
A VT fuse loss condition is detected by using the positive and negative sequence components
of the voltages and currents. VT fuse loss output can be initiated from internally generated logic
or from input contacts.
Time Delay
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
Phase Directional Overcurrent
Phase Directional Overcurrent
Phase Directional Overcurrent
Phase Directional Overcurrent
Phase Directional Overcurrent
Definite Time*
Pickup
1.0 to 240.0 A
0.1 A
&
0.1 A or 3%
(0.2 to 48.0 A)
(
&
0.02 A or 3%)
Time Delay
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
Inverse Time
Pickup
0.50 to 12.00 A
0.01 A
&
0.1 A or
&
3%
(0.10 to 2.40 A)
(
&
0.02 A or
&
3%)
Characteristic Curve
Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC Curves
Time Dial Setting
0.5 to 11.0
0.1
&
3 Cycles or
&
5%
0.05 to 1.10 (IEC curves)
0.01
Phase Directional Element
Maximum Sensitivity
(Torque) Angle (MSA)
0° to 359°
1°
*High speed operation results when delay programmed for one cycle; response time = less than 1–1/2
cycles.
Directional sensing for 67DT or 67IT may be disabled. Sensitivity at MSA is 0.5 VA, uses Positive
Sequence Voltage and current for polarization, prefault memory 8 cycles.
Residual Directional Overcurrent
Definite Time*
Pickup
0.5 to 240.0 A
0.1 A
&
0.1 A or 3%
(0.1 to 48.0 A)
(
&
0.02 A or
&
3%)
Time Delay
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
Inverse Time*
Pickup
0.25 to 12.00 A
0.01 A
&
0.1 A or
&
3%
(0.05 to 2.40 A)
(
&
0.02 A or
&
3%)
Characteristic Curve
Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC Curves
Time Dial
0.5 to 11.0
0.1
&
3 Cycles or
&
5%
0.05 to 1.10 (IEC Curves)
0.01
Ground Directional Element
Max. Sensitivity Angle (MSA) 0 to 359°
1°
Polarization**
1 to 5
1
*Directional control for 67NDT or 67NIT may be disabled.
** Polarization can be zero sequence, negative sequence, current (polarized) or dual polarized. Polariza-
tions 1, 3 and 5 shall not be used with L-L and L-G to L-L VT selection. When using polarizations 4 or 5,
MSA is not applicable and should be set to zero.
†
Select the greater of these accuracy values.
Values in parentheses apply to 1 Amp CT secondary rating.
60
FL
67N
67
Содержание M-3520
Страница 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Страница 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Страница 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Страница 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Страница 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Страница 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...