Commissioning/Configuration
EP5xxx
93
Version: 2.3.0
Index 1C33 SM input parameter
Index (hex) Name
Meaning
Data type
Flags
Default
1C33:0
SM input parameter Synchronization parameters for the inputs
UINT8
RO
0x20 (32
dec
)
1C33:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchron with SM 3 Event (no outputs available)
• 2: DC - Synchron with SYNC0 Event
• 3: DC - Synchron with SYNC1 Event
• 34: Synchron with SM 2 Event (outputs available)
UINT16
RW
0x0022 (34
dec
)
1C33:02
Cycle time
Cycle time (in ns):
• Free Run: Cycle time of the local timer
• Synchron with SM 2 Event: Master cycle time
• DC mode: SYNC0/SYNC1 Cycle Time
UINT32
RW
0x000F4240
(1000000
dec
)
1C33:03
Shift time
Time between SYNC0 event and reading of the inputs (in
ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:04
Sync modes sup-
ported
Supported synchronization modes:
• Bit 0: free run is supported
• Bit 1: Synchron with SM 2 Event is supported
(outputs available)
• Bit 1: Synchron with SM 3 Event is supported (no
outputs available)
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 01: Input shift through local event (outputs
available)
• Bit 4-5 = 10: Input shift with SYNC1 event (no
outputs available)
• Bit 14 = 1: dynamic times (measurement through
writing of 0x1C33:08)
UINT16
RO
0xC00B
(49163
dec
)
1C33:05
Minimum cycle time Minimum cycle time (in ns)
UINT32
RO
0x00030D40
(0
dec
)
1C33:06
Calc and copy time
Time between reading of the inputs and availability of the
inputs for the master (in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:07
Minimum delay time -
UINT32
RO
0x000001B0
(7600
dec
)
1C33:08
Command
With this entry the real required process data provision
time can be measured.
• 0: Measurement of the local cycle time is stopped
• 1: Measurement of the local cycle time is started
The entries 0x1C33:03, 0x1C33:06, 0x1C33:09 are up-
dated with the maximum measured values.
For a subsequent measurement the measured values are
reset
UINT16
RW
0x0000 (0
dec
)
1C33:09
Maximum Delay
time
Time between SYNC1 event and reading of the inputs (in
ns, only DC mode)
UINT32
RO
0x000001B0
(7600
dec
)
1C33:0B
SM event missed
counter
Number of missed SM events in OPERATIONAL (DC
mode only)
UINT16
RO
0x0000 (0
dec
)
1C33:0C
Cycle exceeded
counter
Number of occasions the cycle time was exceeded in OP-
ERATIONAL (cycle was not completed in time or the next
cycle began too early)
UINT16
RO
0x0000 (0
dec
)
1C33:0D
Shift too short
counter
Number of occasions that the interval between SYNC0 and
SYNC1 event was too short (DC mode only)
UINT16
RO
0x0000 (0
dec
)
1C33:20
Sync error
The synchronization was not correct in the last cycle (out-
puts were output too late; DC mode only)
BOOLEAN
RO
0x00 (0
dec
)
Содержание EP5 Series