Commissioning/Configuration
EP5xxx
122
Version: 2.3.0
Index 1C33 SM input parameter
Index (hex) Name
Meaning
Data type
Flags
Default
1C33:0
SM input parameter
Synchronization parameters for the inputs
UINT8
RO
0x20 (32
dec
)
1C33:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchron with SM 3 Event (no outputs
available)
• 2: DC - Synchron with SYNC0 Event
• 3: DC - Synchron with SYNC1 Event
• 34: Synchron with SM 2 Event (outputs
available)
UINT16
RW
0x0022 (34
dec
)
1C33:02
Cycle time
as
0x1C32:02 [
}
121]
UINT32
RW
0x00000000
(0
dec
)
1C33:03
Shift time
Time between SYNC0 event and reading of the in-
puts (in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:04
Sync modes sup-
ported
Supported synchronization modes:
• Bit 0: free run is supported
• Bit 1: Synchron with SM 2 Event is supported
(outputs available)
• Bit 1: Synchron with SM 3 Event is supported
(no outputs available)
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 01: Input shift through local event
(outputs available)
• Bit 4-5 = 10: Input shift with SYNC1 event (no
outputs available)
• Bit 14 = 1: dynamic times (measurement
through writing of
0x1C32:08 [
}
121]
or
0x1C33:08)
UINT16
RO
0xC007
(49159
dec
)
1C33:05
Minimum cycle time
as
0x1C32:05 [
}
121]
UINT32
RO
0x00000000
(0
dec
)
1C33:06
Calc and copy time
Time between reading of the inputs and availability of
the inputs for the master (in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:07
Minimum delay time
UINT32
RO
0x00000000
(0
dec
)
1C33:08
Command
as
0x1C32:08 [
}
121]
UINT16
RW
0x0000 (0
dec
)
1C33:09
Delay time
Time between SYNC1 event and reading of the in-
puts (in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:0B
SM event missed
counter
as
0x1C32:11 [
}
121]
UINT16
RO
0x0000 (0
dec
)
1C33:0C
Cycle exceeded
counter
as
0x1C32:12 [
}
121]
UINT16
RO
0x0000 (0
dec
)
1C33:0D
Shift too short counter as
0x1C32:13 [
}
121]
UINT16
RO
0x0000 (0
dec
)
1C33:20
Sync error
as
0x1C32:32 [
}
121]
BOOLEAN
RO
0x00 (0
dec
)
Index F000 Modular device profile
Index (hex) Name
Meaning
Data type
Flags
Default
F000:0
Modular device profile General information for the modular device profile
UINT8
RO
0x02 (2
dec
)
F000:01
Module index dis-
tance
Index distance of the objects of the individual chan-
nels
UINT16
RO
0x0010 (16
dec
)
F000:02
Maximum number of
modules
Number of channels
UINT16
RO
0x0001 (1
dec
)
Index F008 Code word
Index (hex) Name
Meaning
Data type
Flags
Default
F008:0
Code word
reserved
UINT32
RW
0x00000000
(0
dec
)
Содержание EP5 Series
Страница 2: ......
Страница 6: ...Table of contents EP5xxx 6 Version 2 3 0...