Commissioning/Configuration
EP5xxx
108
Version: 2.3.0
Index 1C32 SM output parameter
Index (hex) Name
Meaning
Data type
Flags
Default
1C32:0
SM output parame-
ter
Synchronization parameters for the outputs
UINT8
RO
0x20 (32
dec
)
1C32:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchron with SM 2 Event
• 2: DC-Mode - Synchron with SYNC0 Event
• 3: DC-Mode - Synchron with SYNC1 Event
UINT16
RW
0x0001 (1
dec
)
1C32:02
Cycle time
Cycle time (in ns):
• Free Run: Cycle time of the local timer
• Synchron with SM 2 Event: Master cycle time
• DC mode: SYNC0/SYNC1 Cycle Time
UINT32
RW
0x00000000
(0
dec
)
1C32:03
Shift time
Time between SYNC0 event and output of the outputs (in
ns, DC mode only)
UINT32
RO
0x00000000
(0
dec
)
1C32:04
Sync modes sup-
ported
Supported synchronization modes:
• Bit 0 = 1: free run is supported
• Bit 1 = 1: Synchron with SM 2 Event is supported
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 10: Output shift with SYNC1 event (only
DC mode)
• Bit 14 = 1: dynamic times (measurement through
writing of 0x1C32:08)
UINT16
RO
0xC007
(49159
dec
)
1C32:05
Minimum cycle time Minimum cycle time (in ns)
UINT32
RO
0x00000000
(0
dec
)
1C32:06
Calc and copy time
Minimum time between SYNC0 and SYNC1 event (in ns,
DC mode only)
UINT32
RO
0x00000000
(0
dec
)
1C32:07
Minimum delay time
UINT32
RO
0x00000000
(0
dec
)
1C32:08
Command
With this entry the real required process data provision
time can be measured.
• 0: Measurement of the local cycle time is stopped
• 1: Measurement of the local cycle time is started
The entries 0x1C32:03, 0x1C32:05, 0x1C32:06,
0x1C32:09,
0x1C33:03 [
}
134]
,
0x1C33:06 [
}
133]
,
0x1C33:09 [
}
134]
are updated with the maximum mea-
sured values.
For a subsequent measurement the measured values are
reset
UINT16
RW
0x0000 (0
dec
)
1C32:09
Maximum delay
time
Time between SYNC1 event and output of the outputs (in
ns, DC mode only)
UINT32
RO
0x00000000
(0
dec
)
1C32:0B
SM event missed
counter
Number of missed SM events in OPERATIONAL (DC
mode only)
UINT16
RO
0x0000 (0
dec
)
1C32:0C
Cycle exceeded
counter
Number of occasions the cycle time was exceeded in OP-
ERATIONAL (cycle was not completed in time or the next
cycle began too early)
UINT16
RO
0x0000 (0
dec
)
1C32:0D
Shift too short
counter
Number of occasions that the interval between SYNC0 and
SYNC1 event was too short (DC mode only)
UINT16
RO
0x0000 (0
dec
)
1C32:20
Sync error
The synchronization was not correct in the last cycle (out-
puts were output too late; DC mode only)
BOOLEAN
RO
0x00 (0
dec
)