Commissioning/Configuration
EP5xxx
90
Version: 2.3.0
4.10
EP5001-0002 - Object description and parameterization
EtherCAT XML Device Description
The display matches that of the CoE objects from the EtherCAT
XML
Device Description. We rec-
ommend downloading the latest XML file from the download area of the Beckhoff website and in-
stalling it according to installation instructions.
Parameterization via the CoE list (CAN over EtherCAT)
The EtherCAT device is parameterized via the
CoE - Online tab [
}
61]
(double-click on the respec-
tive object) or via the
Process Data [
}
58]
tab (allocation of PDOs).
Introduction
The CoE overview contains objects for different intended applications:
• Objects required for parameterization during commissioning
• Objects intended for regular operation, e.g. through ADS access.
• Objects for indicating internal settings (may be fixed)
The following section first describes the objects required for normal operation, followed by a complete
overview of missing objects.
Index 1000 Device type
Index (hex) Name
Meaning
Data type
Flags
Default
1000:0
Device type
Device type of the EtherCAT slave: The Lo-Word contains
the CoE profile used (5001). The Hi-Word contains the
module profile according to the modular device profile.
UINT32
RO
0x01F51389
(32838537
dec
)
Index 1008 Device name
Index (hex) Name
Meaning
Data type
Flags
Default
1008:0
Device name
Device name of the EtherCAT slave
STRING
RO
EP5001-0002
Index 1009 Hardware version
Index (hex) Name
Meaning
Data type
Flags
Default
1009:0
Hardware version
Hardware version of the EtherCAT slave
STRING
RO
-
Index 100A Software version
Index (hex) Name
Meaning
Data type
Flags
Default
100A:0
Software version
Firmware version of the EtherCAT slave
STRING
RO
-
Index 1011 Restore default parameters
Index (hex) Name
Meaning
Data type
Flags
Default
1011:0
Restore default pa-
rameters
Restore default parameters
UINT8
RO
0x01 (1
dec
)
1011:01
SubIndex 001
If this object is set to
"0x64616F6C"
in the set value dia-
log, all backup objects are reset to their delivery state.
UINT32
RW
0x00000000
(0
dec
)
Содержание EP5 Series