Commissioning/Configuration
EP5xxx
111
Version: 2.3.0
4.12
EP5101-0011 - Object description and parameterization
- normal operating mode
EtherCAT XML Device Description
The display matches that of the CoE objects from the EtherCAT
XML
Device Description. We rec-
ommend downloading the latest XML file from the download area of the Beckhoff website and in-
stalling it according to installation instructions.
Parameterization via the CoE list (CAN over EtherCAT)
The EtherCAT device is parameterized via the
CoE - Online tab [
}
61]
(double-click on the respec-
tive object) or via the
Process Data [
}
58]
tab (allocation of PDOs).
4.12.1
Restore object
Index 1011 Restore default parameters
Index (hex) Name
Meaning
Data type
Flags
Default
1011:0
Restore default pa-
rameters
Restore the default settings
UINT8
RO
0x01 (1
dec
)
1011:01
SubIndex 001
If this object is set to
"0x64616F6C"
in the set value dia-
log, all backup objects are reset to their delivery state.
Note: Some FW versions also accept the following input:
0x6C6F6164".
UINT32
RW
0x00000000
(0
dec
)