Commissioning/Configuration
EP5xxx
70
Version: 2.3.0
•
Index
0x8000:13 [
}
94]
, Min. Inhibit time [µs]
See index
0x8000:03 [
}
94]
.
SSI advanced settings
•
Index
0x800D:01 [
}
95]
,
Encoder power supply on
Switches the 24 V supply voltage
•
Index
0x800D:02 [
}
95]
,
Encoder direction pin on
Switches the 24 V supply at the
Direction pin
•
Index
0x800D:03 [
}
95]
,
Encoder reset pin on
Switches the 24 V supply at the
Reset pin
The total size of the data depends on the encoder used. It is also type-specific whether a power-fail bit or
another auxiliary bit is supported. The counter value in the
Counter Value
index
0x6000:11 [
}
94]
is
determined based on the value entered in object
SSI data length
index
0x8000:12 [
}
94]
.
A few example configurations are shown below:
Specification of the encoder
CoE settings of the EP5001-0002
ST
MT
Error bit
0x8000:0F SSI-
frame type
0x8000:11 SSI-
frame size
0x8000:12 SSI-data
length
0x8000:02 Enable power failure
bit
13
0
0
1: Single-turn analy-
sis is active
13
13
0: Power failure bit is not active
12
12
1
0: Multi-turn analy-
sis is active
25
24
1: Power failure bit is active
12
12
0
2: Variable analysis
is active
24
24
0: Power failure bit is not active
12
13
0
2: Variable analysis
is active
25
25
0: Power failure bit is not active
16
16
0
2: Variable analysis
is active
32
32
0: Power failure bit is not active
16
0
0
2: Variable analysis
is active
16
16
0: Power failure bit is not active
13
16
1
2: Variable analysis
is active
30
29
1: Power failure bit is active
12
12
2
2: Variable analysis
is active
26*
26*
0: Power failure bit is not active
*) Analysis of the data and division into position and auxiliary bits must take place in the PLC.
If the encoder offers more than 1 auxiliary bit, this can be done by means of suitable configuration of the
objects 0x8000:11
SSI frame size
and 0x80n0
SSI data length
. The maximum size of 32 bits must be
considered here. If the parameters have the same size, the
Counter Value
index
0x6000:11 [
}
94]
does not
only show the position, but also additional bits. Analysis of the data and division into position and auxiliary
bits must take place in the PLC.
If the settings are not made correctly in the CoE, or if there is an error at the inputs, this is indicated via the
status bits
Data Error
(Index
0x6000:01
[
}
94]
)
Frame error
(Index
0x6000:02
[
}
94]
)
Possible error type
TRUE
FALSE
SSI input error:
- SSI without power supply
- Broken wire at SSI data inputs D+ or D-
If no data communication takes place the SSI input of the terminal is on low level.
FALSE
TRUE
There is an incorrect data frame, the data frame was not concluded with zero, or possibly
- Wire breakage in the clock lines
- Incorrect parameterization in the CoE
TRUE
TRUE
- Broken wire at SSI data inputs D+ or D-
- Data cables interchanged
FALSE
FALSE
If bits are shifted in the counter value despite correct CoE parameterization, this may be to do with
the clock lines being swapped